 Copyright ©  2019                                                                                                                                                                                                                                                                                                                                            - -Cyber Power Systems, Inc. All rights reserved.  K01 0000788 00 
VP700/1000/1200/1600E(I)LCD 
User’s Manual 
IMPORTANT SAFETY INSTRUCTIONS 
This  manual  contains  important  safety  instructions.  Please  read  and  follow  all  instructions  carefully  during 
installation and operation of the unit. Read this manual thoroughly before attempting to unpack, install, or operate 
your UPS. 
CAUTION! The UPS must be connected to a grounded AC power outlet with fuse or circuit breaker protection.   
DO NOT plug the UPS into an outlet that is not grounded. If you need to  -energize this equipment, turn o and de
unplug the UPS. 
CAUTION! DO NOT USE FOR MEDICAL OR LIFE SUPPORT EQUIPMENT! CyberPower does not sell products 
for life support or medical applications.   use in any circumstance that would aect the operation and safety DO NOT
of life support equipment, medical applications, or patient care. 
CAUTION!  Hazardous  live  parts  inside  can  be  energized  by  the  battery  even  when  the  AC  input  power  is 
disconnected. 
CAUTION! To prevent the risk of re or electric shock, install in a temperature and humidity controlled indoor area, 
free of conductive contaminants. (Please see specications for acceptable temperature and humidity range). 
CAUTION!  To  reduce  the risk  of  electric  shock,  do  not  remove  the cover There are  no  user  serviceable  parts . 
inside. 
CAUTION! To avoid electrical shock, turn o the unit and unplug it from the AC power source before installing a 
computer component. 
CAUTION!  DO  NOT  USE  WITH  OR  NEAR  AQUARIUMS!  To  reduce  the  risk  of  re,  do  not  use  with  or  near 
aquariums.  Condensation  from  the  aquarium  can  come  in  contact  with  metal  electrical  contacts  and cause  the 
machine to short out. 
DO NOT USE THE UPS ON ANY TRANSPORTATION!    To reduce the risk of re or electric shock, do not use the 
unit on any transportation such as airplanes or ships. The eect of shock or vibration caused during transit and the 
damp environment can cause the unit to short out. 
INSTALLING YOUR UPS SYSTEM 
UNPACKING 
The box should contain the following: 
(1) UPS Unit  1; (2) USB Cable    User Manual  1;  Multi-language Quick Start Guide (For EU)  1   x  x 1; (3)  x  (4)  x  ; 
(5) Power Cord  1 (Type may differ between models.) x 
OVERVIEW 
The  V 00/1000/1200/1600E(I)P7 LCD  provides  automatic  voltage  regulation  for  inconsistent  utility  power,  and 
provides battery backup during power outages. The V 00/1000/1200/16 (I)P7 00E LCD ensures consistent power to 
your  computer  system  and  its  included  software  will  automatically  save  your  open  les  and  shut  down  your 
computer system during a utility power loss. 
HOW TO DETERMINE THE POWER REQUIREMENTS OF YOUR EQUIPMENT 
1.  Make sure that the total Volt-Amp (VA) requirements of your computer, monitor, and peripheral equipment does 
not exceed the  VA/ /12 16700 1000VA 00VA/ 00VA. 
2.  Ensure that the equipment plugged into the battery power-supplied outlets does not exceed the UPS unit’s rated 
capacity  ( VA/390W  for  VP700E(I)LCD,  00VA/550W  for  VP1000E(I)LCD,1200VA/720W  for 700 10
VP1200E(I)LCD,  1600VA/960W  for  V 00E(I)LCD).  If  rated  unit  capacities  are  exceeded,  an  overload P16
condition may occur and cause the UPS unit to shut down or the circuit breaker trip. 
3.  There are many factors that can aect the amount of power that your computer system will require. For optimal 
system performance keep the load below 80% of the unit’s rated capacity. 
BASIC OPERATION 
  DESCRIPTION 
1.  Power Switch 
Used as the master on/o switch for equipment connected to the battery power supplied outlets. 
2.  Power On Indicator 
This LED is illuminated when the utility power is normal and the UPS outlets are providing power, free of surges 
and spikes. 
3.  LCD Module Display 
High resolution and intelligent LCD display shows all the UPS information with icons and messages. For more 
information, please refer to the Function Setup Guide 
4.  Display / Select Button 
The  button  can  be  used  to  select  the  LCD  display  contents  including  Input  Voltage,  Output  Voltage,  and 
Estimated Run Time. For more information, please refer to the Function Setup Guide. 
5.  Mute / Enter Button 
The  button  can  be  used  to  silence  the  alarm,  conrm  the  settings,  and  enter  into  the functions.  For  more 
information, please refer to the Function Setup Guide. 
6.  Communication Protection Ports 
Communication  protection  ports  will  protect  any  standard  modem,  fax,  telephone  line,  network  or  Ethernet 
connection (RJ11/RJ45). 
7.  Serial/ USB Port to PC 
The Serial and USB port allow connection and communication from DB-9 serial or USB port on the computer to 
the UPS unit. The UPS communicates its status to the PowerPanel
®
 Personal software. 
NOTE: Only one of these two ports can be used as communication and control of the UPS unit at the same 
time. 
8.  Circuit Breaker 
Located on the back of the UPS, the circuit breaker serves to provide overload and fault protection 
9.  AC Input 
Connect AC Power cord to a properly wired and grounded outlet. 
10. Battery Backup and Surge Protected Outlets 
The unit has several battery powered/surge suppression outlets for connected equipment to ensure temporary 
uninterrupted operation  of your equipment during a  power failure.  Check the type  and quantity of  outlets for 
dierent models in the following table. 
11. Surge Protected Outlets 
Provides surge protection for devices that don’t require battery backup. 
Outlet Type 
DE 
FR 
IEC 
AU 
Battery Backup & Surge 
Protected Outlets 
700/1000VA 
4 
4 
6 
3 
1200/1600VA 
4 
4 
4 
3 
Surge Protected Outlets 
700/1000VA 
0 
0 
0 
0 
1200/1600VA 
1 
1 
4 
1 
HARDWARE INSTALLATION GUIDE 
1. Your new UPS may be used immediately upon receipt. However, recharging the battery for at least 8 hours is 
recommended to ensure that the battery's maximum charge capacity is achieved. Charge loss may occur during 
shipping  and  storage.  To recharge the  battery, simply  leave the  unit plugged  into  an AC  outlet. The unit  will 
charge in both the on and o position. 
Note: This UPS is designed with a safety feature to keep the system from being turned on during shipment. The 
rst time you turn the UPS  , you will need to have it connected to AC power or it will not power up. on
2. With the UPS unit o and unplugged, connect the computer, monitor, and any externally powered data storage 
device (Zip  drive, Jazz drive,  Tape drive,  etc.)  into the  battery power supplied outlets.  DO NOT  plug a  laser 
printer,  copier,  space  heater, vacuum,  paper  shredder or other  large electrical device  into the battery 
power supplied outlets. The power demands of these devices will overload and possibly damage the unit. 
3. To protect the network, connect a network cable from the wall jack outlet to the IN jack of the UPS. Then connect 
network cable from the OUT jack on the UPS to the computer or network device. 
4. Plug the UPS into a 2 pole, 3 wire grounded receptacle (wall outlet). Make sure the wall branch outlet is protected 
by a fuse or circuit breaker and does not service equipment with large electrical demands (e.g. air conditioner, 
refrigerator, copier, etc. Avoid using extension cords. 
5. Depress the power switch to turn the unit on. The power on indicator light will illuminate and the unit will "beep". 
6. If an overload is detected, an audible alarm will sound and the unit will emit one long beep. To correct this, turn 
the UPS o and unplug at least one piece of equipment from the battery power supplied outlets. Wait 10 seconds. 
Make sure the circuit breaker is depressed and then turn the UPS on. 
7. Your UPS is equipped with an auto-charge feature. When the UPS is plugged into an AC outlet, the battery will 
automatically recharge. 
8. To maintain optimal battery charge, leave the UPS plugged into an AC outlet at all times. 
9. To store your UPS for an extended period, cover it and store with the battery fully charged. Recharge the battery 
every three months to ensure battery life. 
TECHNICAL SPECIFICATIONS 
Model 
VP700E(I)LCD 
VP1000E(I)LCD 
VP1200E(I)L  CD
VP1600E(I)LCD 
Capacity 
700VA/390W 
1000VA/  550W
1200VA/72  0W
1600VA/96  0W
Input 
Nominal Input Voltage 
220-240V 
Voltage Range 
167-295Vac 
Frequency Range 
50/60Hz +/- 5   (Auto Sensing) Hz
AVR Function 
Yes 
Output 
On Battery Output Voltage 
220-240V 
On Battery Output Frequency 
50/60Hz  -1% +/
Overload Protection 
On Utility: Circuit Breaker, On Battery: Internal Current Limiting 
Physical 
Maximum Dimensions (WxH ) xD
100 60 x 227 x 2  mm 
100 81 55 x 2  x 3  mm 
Weight (kg) 
5.1   kg
6.2   kg
9.6   kg
10.4 kg 
Battery 
Sealed Maintenance Free Lead 
Acid Battery 
12V/7Ah x 1 
12V/9Ah x 1 
12V/7 Ah x 2 .2
12V/9Ah x 2 
Typical Recharge Time 
8 hours 
Warning Diagnostics 
Indicators 
Power On, LCD Display 
Audible Alarms 
On Battery, Low Battery, Overload 
Environmental 
Operating Temperature 
0 C to   40C 
Operating Relative Humidity 
0 to 90% 
Communication 
PowerPanel
®
Personal Software 
Windows 10 / 8 / 7 / Vista / XP / 2000, Server2012 / 2008 / 2003, Linux 
Management 
Auto-Charger 
Yes 
Auto-Restart 
Yes 
USB interface 
Yes 
Certications 
Certications 
CE RC, EAC,  M 
FUNCTION SETUP GUIDE 
BUTTON DESCRIPTION 
Power On: 
Press and hold the POWER button. You will hear a constant tone for 1 second, 
followed by a short beep. Release the button after the short beep. 
Power O: 
Press and hold the POWER button. You will hear a constant tone for 1 second, 
followed by two short beeps. Release the button after the two short beeps. 
DISPLAY: 
Press the button for 3 seconds to change current LCD status between "LCD Sleep in 
1 minute (beep twice  and "LCD Sleep in s  )" 30 minutes (beeps once)". 
  LCD Sleep in 1 minute: In Line mode, LCD screen will   o automatically be
after 1 min of inactivity. 
  LCD Sleep in 30 minute: In Line mode, LCD screen will   o automatically be
after 30 min of inactivity. 
  In Battery mode, LCD screen will be always on. 
SELECT: 
Short press the button to view the information about the UPS or scroll down function / 
option menu in Setup Mode. 
MUTE: 
Press the button for 3 seconds to enable the audible alarm (beeps once) or disable 
(beeps twice) the audible alarm. 
ENTER: 
Short press the button to conrm the settings or enter into the functions. 
Enter into Setup Mode: 
Press both of the “SELECT” and “ENTER” at the same time for approximately 3 
seconds to access the setup mode’s 11 functions. 
Select Function: 
Short press the “SELECT” button to scroll down the function/ option menu. 
Short press the "ENTER" button to enter into set up options. 
Conrm Option: 
When an option is selected, short press the “ENTER” button. 
After the setting has been conrmed, the LCD screen will stop ashing. 
VP700/1000E(I)LCD 
VP1200/1600E(I)LCD 
Produkspesifikasjoner
| Merke: | CyberPower | 
| Kategori: | UPS | 
| Modell: | VP1200ELCD | 
Trenger du hjelp?
Hvis du trenger hjelp med CyberPower VP1200ELCD still et spørsmål nedenfor, og andre brukere vil svare deg
UPS CyberPower Manualer
                        
                         29 Januar 2025
                        
                    
                                                            
                        
                         28 Januar 2025
                        
                    
                                                            
                        
                         28 Januar 2025
                        
                    
                                                            
                        
                         28 Januar 2025
                        
                    
                                                            
                        
                         28 Januar 2025
                        
                    
                                                            
                        
                         28 Januar 2025
                        
                    
                                                            
                        
                         16 Januar 2025
                        
                    
                                                            
                        
                         13 Januar 2025
                        
                    
                                                            
                        
                         13 Januar 2025
                        
                    
                                                            
                        
                         4 Januar 2025
                        
                    
                                                            UPS Manualer
- AEG
- Tripp Lite
- Conceptronic
- LevelOne
- Teltonika
- V7
- Phoenix Contact
- Jung
- IKEA
- Apc
- Middle Atlantic
- Block
- Equip
- FSP/Fortron
- Salicru
Nyeste UPS Manualer
                        
                         9 April 2025
                        
                    
                                                            
                        
                         9 April 2025
                        
                    
                                                            
                        
                         7 April 2025
                        
                    
                                                            
                        
                         7 April 2025
                        
                    
                                                            
                        
                         7 April 2025
                        
                    
                                                            
                        
                         7 April 2025
                        
                    
                                                            
                        
                         7 April 2025
                        
                    
                                                            
                        
                         7 April 2025
                        
                    
                                                            
                        
                         7 April 2025
                        
                    
                                                            
                        
                         3 April 2025