Daikin RXF25E5V1B Bruksanvisning

Les nedenfor 📖 manual på norsk for Daikin RXF25E5V1B (87 sider) i kategorien Ikke kategorisert. Denne guiden var nyttig for 25 personer og ble vurdert med 4.5 stjerner i gjennomsnitt av 2 brukere

Side 1/87
Installer reference guide
R32 split series
RXF20E5V1B
RXF25E5V1B
RXF35E5V1B
RXF42E5V1B
ARXF20E5V1B
ARXF25E5V1B
ARXF35E5V1B
ARXF42E5V1B
Table of contents
Installer reference guide
2
RXF20~42E5V1B+ARXF20~42E5V1B
R32 split series
4P519439-21V – 2022.10
Table of contents
1 About the documentation 4
1.1 About this document ...................................................................................................................................................... 4
1.2 Installer reference guide at a glance .............................................................................................................................. 5
2 General safety precautions 6
2.1 About the documentation .............................................................................................................................................. 6
2.1.1 Meaning of warnings and symbols ................................................................................................................ 6
2.2 For the installer............................................................................................................................................................... 7
2.2.1 General ........................................................................................................................................................... 7
2.2.2 Installation site ............................................................................................................................................... 8
2.2.3 Refrigerant — in case of R410A or R32.......................................................................................................... 11
2.2.4 Electrical ......................................................................................................................................................... 13
3 Specific installer safety instructions 16
4 About the box 21
4.1 Overview: About the box ................................................................................................................................................ 21
4.2 Outdoor unit ................................................................................................................................................................... 21
4.2.1 To unpack the outdoor unit ........................................................................................................................... 21
4.2.2 To remove the accessories from the outdoor unit........................................................................................ 22
5 About the units and options 24
5.1 Overview: About the units and options.......................................................................................................................... 24
5.2 Identification ................................................................................................................................................................... 24
5.2.1 Identification label: Outdoor unit .................................................................................................................. 24
6 Unit installation 25
6.1 Preparing the installation site......................................................................................................................................... 25
6.1.1 Installation site requirements of the outdoor unit........................................................................................ 26
6.1.2 Additional installation site requirements of the outdoor unit in cold climates............................................ 28
6.2 Opening the units ........................................................................................................................................................... 29
6.2.1 About opening the units................................................................................................................................. 29
6.2.2 To open the outdoor unit............................................................................................................................... 29
6.3 Mounting the outdoor unit............................................................................................................................................. 29
6.3.1 About mounting the outdoor unit ................................................................................................................. 29
6.3.2 Precautions when mounting the outdoor unit.............................................................................................. 30
6.3.3 To provide the installation structure ............................................................................................................. 30
6.3.4 To install the outdoor unit ............................................................................................................................. 30
6.3.5 To provide drainage........................................................................................................................................ 31
6.3.6 To prevent the outdoor unit from falling over .............................................................................................. 31
7 Piping installation 33
7.1 Preparing refrigerant piping ........................................................................................................................................... 33
7.1.1 Refrigerant piping requirements.................................................................................................................... 33
7.1.2 Refrigerant piping length and height difference ........................................................................................... 33
7.1.3 Refrigerant piping insulation.......................................................................................................................... 34
7.2 Connecting the refrigerant piping .................................................................................................................................. 34
7.2.1 About connecting the refrigerant piping ....................................................................................................... 34
7.2.2 Precautions when connecting the refrigerant piping.................................................................................... 34
7.2.3 Guidelines when connecting the refrigerant piping...................................................................................... 36
7.2.4 Pipe bending guidelines ................................................................................................................................. 36
7.2.5 To flare the pipe end ...................................................................................................................................... 36
7.2.6 Using the stop valve and service port............................................................................................................ 37
7.2.7 To connect the refrigerant piping to the outdoor unit ................................................................................. 38
7.3 Checking the refrigerant piping...................................................................................................................................... 39
7.3.1 About checking the refrigerant piping........................................................................................................... 39
7.3.2 Precautions when checking the refrigerant piping........................................................................................ 39
7.3.3 To check for leaks ........................................................................................................................................... 40
7.3.4 To perform vacuum drying............................................................................................................................. 40
7.4 Charging refrigerant........................................................................................................................................................ 41
7.4.1 About charging refrigerant............................................................................................................................. 41
7.4.2 About the refrigerant ..................................................................................................................................... 42
7.4.3 To determine the additional refrigerant amount.......................................................................................... 43
7.4.4 To determine the complete recharge amount.............................................................................................. 43
7.4.5 To charge additional refrigerant .................................................................................................................... 44
7.4.6 To fix the fluorinated greenhouse gases label............................................................................................... 44
Table of contents
Installer reference guide
3
RXF20~42E5V1B+ARXF20~42E5V1B
R32 split series
4P519439-21V – 2022.10
8 Electrical installation 45
8.1 Preparing electrical wiring .............................................................................................................................................. 45
8.1.1 About preparing electrical wiring................................................................................................................... 45
8.2 Connecting the electrical wiring..................................................................................................................................... 46
8.2.1 About connecting the electrical wiring.......................................................................................................... 46
8.2.2 Precautions when connecting the electrical wiring....................................................................................... 46
8.2.3 Guidelines when connecting the electrical wiring......................................................................................... 47
8.2.4 Specifications of standard wiring components.............................................................................................. 48
8.2.5 To connect the electrical wiring to the outdoor unit .................................................................................... 48
9 Finishing the outdoor unit installation 50
9.1 To finish the outdoor unit installation............................................................................................................................ 50
9.2 To close the outdoor unit ............................................................................................................................................... 50
10 Commissioning 51
10.1 Overview: Commissioning .............................................................................................................................................. 51
10.2 Precautions when commissioning.................................................................................................................................. 51
10.3 Checklist before commissioning..................................................................................................................................... 51
10.4 Checklist during commissioning ..................................................................................................................................... 52
10.5 To perform a test run...................................................................................................................................................... 52
10.6 Starting up the outdoor unit........................................................................................................................................... 53
11 Hand-over to the user 54
12 Maintenance and service 55
12.1 Overview: Maintenance and service .............................................................................................................................. 55
12.2 Maintenance safety precautions.................................................................................................................................... 55
12.3 Checklist for yearly maintenance of the outdoor unit................................................................................................... 55
13 Troubleshooting 57
13.1 Overview: Troubleshooting ............................................................................................................................................ 57
13.2 Precautions when troubleshooting ................................................................................................................................ 57
13.3 Solving problems based on symptoms........................................................................................................................... 57
13.3.1 Symptom: Indoor units fall, vibrate or make noise ....................................................................................... 57
13.3.2 Symptom: The unit is NOT heating or cooling as expected........................................................................... 58
13.3.3 Symptom: Water leakage............................................................................................................................... 58
13.3.4 Symptom: Electrical leakage .......................................................................................................................... 58
13.3.5 Symptom: Unit does NOT function or burn damage..................................................................................... 58
14 Disposal 59
14.1 Overview: Disposal.......................................................................................................................................................... 59
14.2 To pump down ................................................................................................................................................................ 59
14.3 To start and stop forced cooling..................................................................................................................................... 60
14.3.1 To start and stop forced cooling using the indoor unit ON/OFF switch ....................................................... 60
14.3.2 To start and stop forced cooling using the indoor unit user interface ......................................................... 60
15 Technical data 61
15.1 Wiring diagram................................................................................................................................................................ 62
16 Glossary 63
1 | About the documentation
Installer reference guide
4
RXF20~42E5V1B+ARXF20~42E5V1B
R32 split series
4P519439-21V – 2022.10
1 About the documentation
1.1 About this document
WARNING
Make sure installation, servicing, maintenance, repair and applied materials follow
the instructions from Daikin (including all documents listed in “Documentation set”)
and, in addition, comply with applicable legislation and are performed by qualified
persons only. In Europe and areas where IEC standards apply, EN/IEC 60335-2-40 is
the applicable standard.
INFORMATION
Make sure that the user has the printed documentation and ask him/her to keep it
for future reference.
Target audience
Authorised installers
INFORMATION
This document only describes installation instructions specific to the outdoor unit.
For installation of the indoor unit (mounting the indoor unit, connecting the
refrigerant piping to the indoor unit, connecting the electrical wiring to the indoor
unit …), see the installation manual of the indoor unit.
Documentation set
This document is part of a documentation set. The complete set consists of:
General safety precautions:
- Safety instructions that you MUST read before installing
- Format: Paper (in the box of the outdoor unit)
Outdoor unit installation manual:
- Installation instructions
- Format: Paper (in the box of the outdoor unit)
Installer reference guide:
- Preparation of the installation, reference data,…
- Format: Digital files on https://www.daikin.eu. Use the search function to
find your model.
Latest revisions of the supplied documentation may be available on the regional
Daikin website or via your dealer.
The original documentation is written in English. All other languages are
translations.
Technical engineering data
A subset of the latest technical data is available on the regional Daikin website
(publicly accessible).
The full set of latest technical data is available on the Daikin Business Portal
(authentication required).
1 | About the documentation
Installer reference guide
5
RXF20~42E5V1B+ARXF20~42E5V1B
R32 split series
4P519439-21V – 2022.10
1.2 Installer reference guide at a glance
Chapter Description
General safety precautions Safety instructions that you MUST read before
installing
About the documentation What documentation exists for the installer
About the box How to unpack the units and remove their
accessories
About the unit System layout
Operation range
Preparation What to do and know before going on‑site
Installation What to do and know to install the system
Configuration What to do and know to configure the system
after it is installed
Commissioning What to do and know to commission the system
after it is configured
Hand‑over to the user What to give and explain to the user
Disposal How to dispose of the system
Technical data Specifications of the system
Glossary Definition of terms
2 | General safety precautions
Installer reference guide
6
RXF20~42E5V1B+ARXF20~42E5V1B
R32 split series
4P519439-21V – 2022.10
2 General safety precautions
2.1 About the documentation
The original documentation is written in English. All other languages are
translations.
The precautions described in this document cover very important topics, follow
them carefully.
The installation of the system, and all activities described in the installation
manual and in the installer reference guide MUST be performed by an authorised
installer.
2.1.1 Meaning of warnings and symbols
DANGER
Indicates a situation that results in death or serious injury.
DANGER: RISK OF ELECTROCUTION
Indicates a situation that could result in electrocution.
DANGER: RISK OF BURNING/SCALDING
Indicates a situation that could result in burning/scalding because of extreme hot or
cold temperatures.
DANGER: RISK OF EXPLOSION
Indicates a situation that could result in explosion.
WARNING
Indicates a situation that could result in death or serious injury.
WARNING: FLAMMABLE MATERIAL
CAUTION
Indicates a situation that could result in minor or moderate injury.
NOTICE
Indicates a situation that could result in equipment or property damage.
INFORMATION
Indicates useful tips or additional information.
Symbols used on the unit:
2 | General safety precautions
Installer reference guide
7
RXF20~42E5V1B+ARXF20~42E5V1B
R32 split series
4P519439-21V – 2022.10
Symbol Explanation
Before installation, read the installation and operation
manual, and the wiring instruction sheet.
Before performing maintenance and service tasks, read the
service manual.
For more information, see the installer and user reference
guide.
The unit contains rotating parts. Be careful when servicing or
inspecting the unit.
Symbols used in the documentation:
Symbol Explanation
Indicates a figure title or a reference to it.
Example: " 1–3 Figure title" means "Figure 3 in chapter 1".
Indicates a table title or a reference to it.
Example: " 1–3 Table title" means "Table 3 in chapter 1".
2.2 For the installer
2.2.1 General
If you are NOT sure how to install or operate the unit, contact your dealer.
DANGER: RISK OF BURNING/SCALDING
Do NOT touch the refrigerant piping, water piping or internal parts during and
immediately after operation. It could be too hot or too cold. Give it time to return
to normal temperature. If you MUST touch it, wear protective gloves.
Do NOT touch any accidental leaking refrigerant.
WARNING
Improper installation or attachment of equipment or accessories could result in
electrical shock, short-circuit, leaks, fire or other damage to the equipment. ONLY
use accessories, optional equipment and spare parts made or approved by Daikin.
WARNING
Make sure installation, testing and applied materials comply with applicable
legislation (on top of the instructions described in the Daikin documentation).
WARNING
Tear apart and throw away plastic packaging bags so that nobody, especially
children, can play with them. Possible risk: suffocation.
WARNING
Provide adequate measures to prevent that the unit can be used as a shelter by small
animals. Small animals that make contact with electrical parts can cause
malfunctions, smoke or fire.
2 | General safety precautions
Installer reference guide
8
RXF20~42E5V1B+ARXF20~42E5V1B
R32 split series
4P519439-21V – 2022.10
CAUTION
Wear adequate personal protective equipment (protective gloves, safety glasses,…)
when installing, maintaining or servicing the system.
CAUTION
Do NOT touch the air inlet or aluminium fins of the unit.
CAUTION
Do NOT place any objects or equipment on top of the unit.
Do NOT sit, climb or stand on the unit.
NOTICE
Works executed on the outdoor unit are best done under dry weather conditions to
avoid water ingress.
In accordance with the applicable legislation, it might be necessary to provide a
logbook with the product containing at least: information on maintenance, repair
work, results of tests, stand-by periods,…
Also, at least, following information MUST be provided at an accessible place at the
product:
Instructions for shutting down the system in case of an emergency
Name and address of fire department, police and hospital
Name, address and day and night telephone numbers for obtaining service
In Europe, EN378 provides the necessary guidance for this logbook.
2.2.2 Installation site
Provide sufficient space around the unit for servicing and air circulation.
Make sure the installation site withstands the weight and vibration of the unit.
Make sure the area is well ventilated. Do NOT block any ventilation openings.
Make sure the unit is level.
Do NOT install the unit in the following places:
In potentially explosive atmospheres.
In places where there is machinery that emits electromagnetic waves.
Electromagnetic waves may disturb the control system, and cause malfunction of
the equipment.
In places where there is a risk of fire due to the leakage of flammable gases
(example: thinner or gasoline), carbon fibre, ignitable dust.
In places where corrosive gas (example: sulphurous acid gas) is produced.
Corrosion of copper pipes or soldered parts may cause the refrigerant to leak.
Instructions for equipment using R32 refrigerant
WARNING: MILDLY FLAMMABLE MATERIAL
The refrigerant inside this unit is mildly flammable.
2 | General safety precautions
Installer reference guide
9
RXF20~42E5V1B+ARXF20~42E5V1B
R32 split series
4P519439-21V – 2022.10
WARNING
Do NOT pierce or burn refrigerant cycle parts.
Do NOT use cleaning materials or means to accelerate the defrosting process
other than those recommended by the manufacturer.
Be aware that the refrigerant inside the system is odourless.
WARNING
The appliance shall be stored so as to prevent mechanical damage and in a well-
ventilated room without continuously operating ignition sources (example: open
flames, an operating gas appliance or an operating electric heater) and have a room
size as specified below.
WARNING
Make sure installation, servicing, maintenance and repair comply with instructions
from Daikin and with applicable legislation and are executed ONLY by authorised
persons.
WARNING
If one or more rooms are connected to the unit using a duct system, make sure:
there are no operating ignition sources (example: open flames, an operating gas
appliance or an operating electric heater) in case the floor area is less than the
minimum floor area A (m²).
no auxiliary devices, which may be a potential ignition source, are installed in the
duct work (example: hot surfaces with a temperature exceeding 700°C and
electric switching device);
only auxiliary devices approved by the manufacturer are used in the duct work;
air inlet AND outlet are connected directly to the same room by ducting. Do NOT
use spaces such as a false ceiling as a duct for the air inlet or outlet.
WARNING
Take precautions to avoid excessive vibration or pulsation to refrigeration piping.
Protect the protection devices, piping and fittings as much as possible against
adverse environmental effects.
Provide space for expansion and contraction of long runs of piping.
Design and install piping in refrigerating systems such as to minimise the
likelihood of hydraulic shock damaging the system.
Mount the indoor equipment and pipes securely and protect them to avoid
accidental rupture of equipment or pipes in case of events such as moving
furniture or reconstruction activities.
CAUTION
Do NOT use potential sources of ignition in searching for or detection of refrigerant
leaks.
NOTICE
Do NOT re-use joints and copper gaskets which have been used already.
Joints made in installation between parts of refrigerant system shall be accessible
for maintenance purposes.
2 | General safety precautions
Installer reference guide
10
RXF20~42E5V1B+ARXF20~42E5V1B
R32 split series
4P519439-21V – 2022.10
Installation space requirements
WARNING
If appliances contain R32 refrigerant, the floor area of the room in which the
appliances are installed, operated and stored MUST be larger than the minimum
floor area defined in table below A (m
2
). This applies to:
Indoor units without a refrigerant leakage sensor; in case of indoor units with
refrigerant leakage sensor, consult the installation manual
Outdoor units installed or stored indoors (e.g. winter garden, garage, machinery
room)
NOTICE
Protect pipework from physical damage.
Keep the pipework installation to a minimum.
To determine the minimum floor area
1 Determine the total refrigerant charge in the system (= factory refrigerant
charge + additional refrigerant amount charged).
Contains fluorinated greenhouse gases
2
1
1
1
2
2
kg
tCO
2
eq
1000
GWP × kg
=
=
+
kg
=
kg
=
GWP: xxx
R32
2 Determine which graph or table to use.
For indoor units: Is the unit ceiling-mounted, wall-mounted or floor-
standing?
For outdoor units installed or stored indoors, this depends on the installation
height:
If the installation height is… Then use the graph or table for…
<1.8m Floor-standing units
1.8≤x<2.2m Wall-mounted units
≥2.2m Ceiling-mounted units
3 Use the graph or table to determine the minimum floor area.
2 | General safety precautions
Installer reference guide
11
RXF20~42E5V1B+ARXF20~42E5V1B
R32 split series
4P519439-21V – 2022.10
0
10
20
30
40
50
60
70
80
90
100
110
120
130
140
150
160
170
180
190
200
210
220
230
240
250
260
270
280
290
300
310
320
330
340
350
360
370
380
390
400
410
420
430
440
450
460
470
480
490
500
510
520
530
540
550
560
570
580
590
600
610
620
630
640
650
660
670
680
690
700
710
720
730
740
750
760
770
1.843
9.55
2.21.8
2.4 2.8 3.2 3.6 4 4.4 4.8 5.2 5.6 6 6.4 6.8 7.2 7.6 8 8.4 8.8 9.22
2.6 3 3.4 3.8 4.2
4.6
5 5.4 5.8 6.2 6.6 7 7.4 7.8 8.2 8.6 9 9.4
Floor-standing unit
(c)
Wall-mounted unit
(b)
Ceiling-mounted unit
(a)
m [kg]
A
min
[m
2
]
Ceiling-mounted
unit
(a)
4.6 13.4
4.6 180
4.8 14.6
4.8 196
5.0 15.8
5.0 213
≤1.842
5.2 17.1
≤1.842
5.2 230
1.843 3.64
5.4 18.5
1.843 28.9
5.4 248
2.0 3.95
5.6 19.9
2.0 34.0
5.6 267
2.2 4.34
5.8 21.3
2.2 41.2
5.8 286
2.4 4.74
6.0 22.8
2.4 49.0
6.0 306
2.6 5.13
6.2 24.3
2.6 57.5
6.2 327
2.8 5.53
6.4 25.9
2.8 66.7
6.4 349
3.0 5.92
6.6 27.6
3.0 76.6
6.6 371
3.2 6.48
6.8 29.3
3.2 87.2
6.8 394
3.4 7.32
7.0 31.0
3.4 98.4
7.0 417
3.6 8.20
7.2 32.8
3.6 110
7.2 441
3.8 9.14
7.4 34.7
3.8 123
7.4 466
4.0 10.1
7.6 36.6
4.0 136
7.6 492
4.2 11.2
7.8 38.5
4.2 150
7.8 518
4.4 12.3
4.4 165
m (kg)
A
min
(m
2
)
4.6 20.0
4.8 21.8
5.0 23.6
≤1.842
5.2 25.6
1.843 4.45
5.4 27.6
2.0 4.83
5.6 29.7
2.2 5.31
5.8 31.8
2.4 5.79
6.0 34.0
2.6 6.39
6.2 36.4
2.8 7.41
6.4 38.7
3.0 8.51
6.6 41.2
3.2 9.68
6.8 43.7
3.4 10.9
7.0 46.3
3.6 12.3
7.2 49.0
3.8 13.7
7.4 51.8
4.0 15.1
7.6 54.6
4.2 16.7
7.8 57.5
4.4 18.3
8 40.5
8.2 42.6
8.4 44.7
8.6 46.8
8.8 49.0
9 51.3
9.2 53.6
9.4 55.9
9.55 57.7
8 60.5
8.2 63.6
8.4 66.7
8.6 69.9
8.8 73.2
9 76.6
9.2 80.0
9.4 83.6
9.55 86.2
8 545
8.2 572
8.4 601
8.6 629
8.8 659
9 689
9.2 720
9.4 752
9.55 776
Wall-mounted
unit
(b)
m (kg)
A
min
(m
2
)
Floor-standing
unit
(c)
m (kg)
A
min
(m
2
)
m Total refrigerant charge in the system
A
min
Minimum floor area
(a) Ceiling-mounted unit (= Ceiling-mounted unit)
(b) Wall-mounted unit (= Wall-mounted unit)
(c) Floor-standing unit (= Floor-standing unit)
2.2.3 Refrigerant — in case of R410A or R32
If applicable. See the installation manual or installer reference guide of your
application for more information.
DANGER: RISK OF EXPLOSION
Pump down – Refrigerant leakage. If you want to pump down the system, and there
is a leak in the refrigerant circuit:
Do NOT use the unit's automatic pump down function, with which you can collect
all refrigerant from the system into the outdoor unit. Possible consequence: Self-
combustion and explosion of the compressor because of air going into the
operating compressor.
Use a separate recovery system so that the unit's compressor does NOT have to
operate.
WARNING
During tests, NEVER pressurise the product with a pressure higher than the
maximum allowable pressure (as indicated on the nameplate of the unit).
2 | General safety precautions
Installer reference guide
12
RXF20~42E5V1B+ARXF20~42E5V1B
R32 split series
4P519439-21V – 2022.10
WARNING
Take sufficient precautions in case of refrigerant leakage. If refrigerant gas leaks,
ventilate the area immediately. Possible risks:
Excessive refrigerant concentrations in a closed room can lead to oxygen
deficiency.
Toxic gas might be produced if refrigerant gas comes into contact with fire.
WARNING
ALWAYS recover the refrigerant. Do NOT release them directly into the environment.
Use a vacuum pump to evacuate the installation.
WARNING
Make sure there is no oxygen in the system. Refrigerant may ONLY be charged after
performing the leak test and the vacuum drying.
Possible consequence: Self-combustion and explosion of the compressor because of
oxygen going into the operating compressor.
NOTICE
To avoid compressor breakdown, do NOT charge more than the specified amount
of refrigerant.
When the refrigerant system is to be opened, refrigerant MUST be treated
according to the applicable legislation.
NOTICE
Make sure refrigerant piping installation complies with applicable legislation. In
Europe, EN378 is the applicable standard.
NOTICE
Make sure the field piping and connections are NOT subjected to stress.
NOTICE
After all the piping has been connected, make sure there is no gas leak. Use nitrogen
to perform a gas leak detection.
In case recharge is required, see the nameplate of the unit. It states the type of
refrigerant and necessary amount.
The unit is factory charged with refrigerant and depending on pipe sizes and pipe
lengths some systems require additional charging of refrigerant.
ONLY use tools exclusively for the refrigerant type used in the system, this to
ensure pressure resistance and prevent foreign materials from entering into the
system.
Charge the liquid refrigerant as follows:
If Then
A siphon tube is present
(i.e., the cylinder is marked with "Liquid
filling siphon attached")
Charge with the cylinder upright.
2 | General safety precautions
Installer reference guide
13
RXF20~42E5V1B+ARXF20~42E5V1B
R32 split series
4P519439-21V – 2022.10
If Then
A siphon tube is NOT present Charge with the cylinder upside down.
Open refrigerant cylinders slowly.
Charge the refrigerant in liquid form. Adding it in gas form may prevent normal
operation.
CAUTION
When the refrigerant charging procedure is done or when pausing, close the valve of
the refrigerant tank immediately. If the valve is NOT closed immediately, remaining
pressure might charge additional refrigerant. Possible consequence: Incorrect
refrigerant amount.
2.2.4 Electrical
DANGER: RISK OF ELECTROCUTION
Turn OFF all power supply before removing the switch box cover, connecting
electrical wiring or touching electrical parts.
Disconnect the power supply for more than 10minutes, and measure the voltage
at the terminals of main circuit capacitors or electrical components before
servicing. The voltage MUST be less than 50VDC before you can touch electrical
components. For the location of the terminals, see the wiring diagram.
Do NOT touch electrical components with wet hands.
Do NOT leave the unit unattended when the service cover is removed.
WARNING
If NOT factory installed, a main switch or other means for disconnection, having a
contact separation in all poles providing full disconnection under overvoltage
categoryIII condition, MUST be installed in the fixed wiring.
2 | General safety precautions
Installer reference guide
14
RXF20~42E5V1B+ARXF20~42E5V1B
R32 split series
4P519439-21V – 2022.10
WARNING
ONLY use copper wires.
Make sure the field wiring complies with the applicable legislation.
All field wiring MUST be performed in accordance with the wiring diagram
supplied with the product.
NEVER squeeze bundled cables and make sure they do NOT come in contact with
the piping and sharp edges. Make sure no external pressure is applied to the
terminal connections.
Make sure to install earth wiring. Do NOT earth the unit to a utility pipe, surge
absorber, or telephone earth. Incomplete earth may cause electrical shock.
Make sure to use a dedicated power circuit. NEVER use a power supply shared by
another appliance.
Make sure to install the required fuses or circuit breakers.
Make sure to install an earth leakage protector. Failure to do so may cause
electrical shock or fire.
When installing the earth leakage protector, make sure it is compatible with the
inverter (resistant to high frequency electric noise) to avoid unnecessary opening
of the earth leakage protector.
CAUTION
When connecting the power supply: connect the earth cable first, before making
the current-carrying connections.
When disconnecting the power supply: disconnect the current-carrying cables
first, before separating the earth connection.
The length of the conductors between the power supply stress relief and the
terminal block itself MUST be as such that the current-carrying wires are
tautened before the earth wire is in case the power supply is pulled loose from
the stress relief.
NOTICE
Precautions when laying power wiring:
Do NOT connect wiring of different thicknesses to the power terminal block (slack
in the power wiring may cause abnormal heat).
When connecting wiring which is the same thickness, do as shown in the figure
above.
For wiring, use the designated power wire and connect firmly, then secure to
prevent outside pressure being exerted on the terminal board.
Use an appropriate screwdriver for tightening the terminal screws. A screwdriver
with a small head will damage the head and make proper tightening impossible.
Over-tightening the terminal screws may break them.
WARNING
After finishing the electrical work, confirm that each electrical component and
terminal inside the electrical components box is connected securely.
Make sure all covers are closed before starting up the unit.
2 | General safety precautions
Installer reference guide
15
RXF20~42E5V1B+ARXF20~42E5V1B
R32 split series
4P519439-21V – 2022.10
NOTICE
ONLY applicable if the power supply is three‑phase, and the compressor has an ON/
OFF starting method.
If there exists the possibility of reversed phase after a momentary black out and the
power goes ON and OFF while the product is operating, attach a reversed phase
protection circuit locally. Running the product in reversed phase can break the
compressor and other parts.
3 | Specific installer safety instructions
Installer reference guide
16
RXF20~42E5V1B+ARXF20~42E5V1B
R32 split series
4P519439-21V – 2022.10
3 Specific installer safety instructions
Always observe the following safety instructions and regulations.
Unit installation (see
"6Unit installation"[
4
25]
)
WARNING
Installation shall be done by an installer, the choice of materials and installation shall
comply with the applicable legislation. In Europe, EN378 is the applicable standard.
Installation site (see
"6.1Preparing the installation site"[
4
25]
)
CAUTION
Check if the installation location can support the unit's weight. Poor installation is
hazardous. It can also cause vibrations or unusual operating noise.
Provide sufficient service space.
Do NOT install the unit so that it is in contact with a ceiling or a wall, as this may
cause vibrations.
WARNING
The appliance shall be stored in a room without continuously operating ignition
sources (example: open flames, an operating gas appliance or an operating electric
heater).
Connecting the refrigerant piping (see
"7.2Connecting the refrigerant
piping"[
4
34]
)
CAUTION
No brazing or welding on site for units with R32 refrigerant charge during
shipment.
During installation of the refrigeration system, joining of parts with at least one
part charged shall be performed taking into account the following requirements:
inside occupied spaces non-permanent joints are NOT allowed for R32 refrigerant
except for site made joints directly connecting the indoor unit to piping. Site
made joints directly connecting piping to indoor units shall be of non-permanent
type.
NOTICE
Use the flare nut fixed to the unit.
To prevent gas leakage, apply refrigeration oil ONLY to the inside of the flare. Use
refrigeration oil for R32 (FW68DA).
Do NOT reuse joints.
NOTICE
Do NOT use mineral oil on flared part.
Do NOT reuse piping from previous installations.
NEVER install a drier to this R32 unit to guarantee its lifetime. The drying material
may dissolve and damage the system.
3 | Specific installer safety instructions
Installer reference guide
17
RXF20~42E5V1B+ARXF20~42E5V1B
R32 split series
4P519439-21V – 2022.10
WARNING
Connect the refrigerant piping securely before running the compressor. If the
refrigerant piping is NOT connected and the stop valve is open when the compressor
is run, air will be sucked in. This will cause abnormal pressure in the refrigeration
cycle, which may result in equipment damage and even injury.
CAUTION
Incomplete flaring may cause refrigerant gas leakage.
Do NOT re-use flares. Use new flares to prevent refrigerant gas leakage.
Use flare nuts that are included with the unit. Using different flare nuts may
cause refrigerant gas leakage.
CAUTION
Do NOT open the valves before flaring is complete. This would cause refrigerant gas
leakage.
DANGER: RISK OF EXPLOSION
Do NOT open the stop valves before the vacuum drying is finished.
Charging refrigerant (see
"7.4Charging refrigerant"[
4
41]
)
WARNING
The refrigerant inside the unit is mildly flammable, but normally does NOT leak. If
the refrigerant leaks in the room and comes in contact with fire from a burner, a
heater, or a cooker, this may result in fire, or the formation of a harmful gas.
Turn OFF any combustible heating devices, ventilate the room, and contact the
dealer where you purchased the unit.
Do NOT use the unit until a service person confirms that the part from which the
refrigerant leaked has been repaired.
WARNING
Only use R32 as refrigerant. Other substances may cause explosions and
accidents.
R32 contains fluorinated greenhouse gases. Its global warming potential (GWP)
value is 675. Do NOT vent these gases into the atmosphere.
When charging refrigerant, ALWAYS use protective gloves and safety glasses.
NOTICE
To avoid compressor breakdown, do NOT charge more than the specified amount of
refrigerant.
WARNING
NEVER directly touch any accidental leaking refrigerant. This could result in severe
wounds caused by frostbite.
Electrical installation (see
"8Electrical installation"[
4
45]
)
WARNING
The appliance MUST be installed in accordance with national wiring regulations.
3 | Specific installer safety instructions
Installer reference guide
18
RXF20~42E5V1B+ARXF20~42E5V1B
R32 split series
4P519439-21V – 2022.10
WARNING
All wiring MUST be performed by an authorised electrician and MUST comply
with the applicable national wiring regulation.
Make electrical connections to the fixed wiring.
All components procured on-site and all electrical construction MUST comply
with the applicable legislation.
WARNING
If the power supply has a missing or wrong N-phase, equipment might break
down.
Establish proper earthing. Do NOT earth the unit to a utility pipe, surge absorber,
or telephone earth. Incomplete earthing may cause electrical shock.
Install the required fuses or circuit breakers.
Secure the electrical wiring with cable ties so that the cables do NOT come in
contact with sharp edges or piping, particularly on the high-pressure side.
Do NOT use taped wires, extension cords, or connections from a star system.
They can cause overheating, electrical shock or fire.
Do NOT install a phase advancing capacitor, because this unit is equipped with an
inverter. A phase advancing capacitor will reduce performance and may cause
accidents.
WARNING
ALWAYS use multicore cable for power supply cables.
WARNING
Use an all-pole disconnection type breaker with at least 3mm between the contact
point gaps that provides full disconnection under overvoltage category III.
WARNING
If the supply cord is damaged, it MUST be replaced by the manufacturer, its service
agent or similarly qualified persons in order to avoid a hazard.
WARNING
Do NOT connect the power supply to the indoor unit. This could result in electrical
shock or fire.
WARNING
Do NOT use locally purchased electrical parts inside the product.
Do NOT branch the power supply for the drain pump, etc. from the terminal
block. This could result in electrical shock or fire.
WARNING
Keep the interconnection wiring away from copper pipes without thermal insulation
as such pipes will be very hot.
DANGER: RISK OF ELECTROCUTION
All electrical parts (including thermistors) are powered by the power supply. Do NOT
touch them with bare hands.
3 | Specific installer safety instructions
Installer reference guide
20
RXF20~42E5V1B+ARXF20~42E5V1B
R32 split series
4P519439-21V – 2022.10
DANGER: RISK OF ELECTROCUTION
Use this compressor on a grounded system only.
Turn the power off before servicing the compressor.
Reattach the switch box cover and service lid after servicing.
CAUTION
ALWAYS wear safety glasses and protective gloves.
DANGER: RISK OF EXPLOSION
Use a pipe cutter to remove the compressor.
Do NOT use the brazing torch.
Use approved refrigerants and lubricants only.
DANGER: RISK OF BURNING/SCALDING
Do NOT touch the compressor with bare hands.
Troubleshooting (see
"13Troubleshooting"[
4
57]
)
DANGER: RISK OF ELECTROCUTION
DANGER: RISK OF BURNING/SCALDING
WARNING
When carrying out an inspection on the switch box of the unit, ALWAYS make
sure that the unit is disconnected from the mains. Turn off the respective circuit
breaker.
When a safety device was activated, stop the unit and find out why the safety
device was activated before resetting it. NEVER shunt safety devices or change
their values to a value other than the factory default setting. If you are unable to
find the cause of the problem, call your dealer.
WARNING
Prevent hazards due to inadvertent resetting of the thermal cut-out: power to this
appliance MUST NOT be supplied through an external switching device, such as a
timer, or connected to a circuit that is regularly turned ON and OFF by the utility.
DANGER: RISK OF ELECTROCUTION
When the unit is NOT operating, the LEDs on the PCB are turned OFF in order to
save power.
Even when the LEDs are OFF, the terminal block and the PCB may be powered.
4 | About the box
Installer reference guide
21
RXF20~42E5V1B+ARXF20~42E5V1B
R32 split series
4P519439-21V – 2022.10
4 About the box
4.1 Overview: About the box
This chapter describes what you have to do after the box with the outdoor unit is
delivered on-site.
Keep the following in mind:
At delivery, the unit MUST be checked for damage and completeness. Any
damage or missing parts MUST be reported immediately to the claims agent of
the carrier.
Bring the packed unit as close as possible to its final installation position to
prevent damage during transport.
When handling the unit, take into account the following:
Fragile, handle the unit with care.
Keep the unit upright in order to avoid damage.
Prepare in advance the path along which you want to bring the unit to its final
installation position.
4.2 Outdoor unit
4.2.1 To unpack the outdoor unit
4 | About the box
Installer reference guide
22
RXF20~42E5V1B+ARXF20~42E5V1B
R32 split series
4P519439-21V – 2022.10
1
2
WARNING
Make sure installation, servicing, maintenance and repair comply with instructions
from Daikin and with applicable legislation and are executed ONLY by authorised
persons.
4.2.2 To remove the accessories from the outdoor unit
1 Lift the outdoor unit.
CAUTION
ONLY handle the outdoor unit as follows:
2 Remove the accessories at the bottom of the package.
4 | About the box
Installer reference guide
23
RXF20~42E5V1B+ARXF20~42E5V1B
R32 split series
4P519439-21V – 2022.10
b ec d
a
a General safety precautions
b Outdoor unit installation manual
c Fluorinated greenhouse gases label
d Multilingual fluorinated greenhouse gases label
e Drain plug (located on the bottom of the packing case)
5 | About the units and options
Installer reference guide
24
RXF20~42E5V1B+ARXF20~42E5V1B
R32 split series
4P519439-21V – 2022.10
5 About the units and options
5.1 Overview: About the units and options
This chapter contains information about:
Identification of the outdoor unit
5.2 Identification
NOTICE
When installing or servicing several units at the same time, make sure NOT to switch
the service panels between different models.
5.2.1 Identification label: Outdoor unit
Location
6 | Unit installation
Installer reference guide
25
RXF20~42E5V1B+ARXF20~42E5V1B
R32 split series
4P519439-21V – 2022.10
6 Unit installation
In this chapter
6.1 Preparing the installation site ................................................................................................................................................ 25
6.1.1 Installation site requirements of the outdoor unit ............................................................................................... 26
6.1.2 Additional installation site requirements of the outdoor unit in cold climates ................................................... 28
6.2 Opening the units ................................................................................................................................................................... 29
6.2.1 About opening the units ........................................................................................................................................ 29
6.2.2 To open the outdoor unit ...................................................................................................................................... 29
6.3 Mounting the outdoor unit .................................................................................................................................................... 29
6.3.1 About mounting the outdoor unit ......................................................................................................................... 29
6.3.2 Precautions when mounting the outdoor unit...................................................................................................... 30
6.3.3 To provide the installation structure ..................................................................................................................... 30
6.3.4 To install the outdoor unit ..................................................................................................................................... 30
6.3.5 To provide drainage ............................................................................................................................................... 31
6.3.6 To prevent the outdoor unit from falling over ...................................................................................................... 31
6.1 Preparing the installation site
Choose an installation location with sufficient space to transport the unit in and
out of the site.
Do NOT install the unit in places often used as work place. In case of construction
works (e.g. grinding works) where a lot of dust is created, the unit MUST be
covered.
CAUTION
Check if the installation location can support the unit's weight. Poor installation is
hazardous. It can also cause vibrations or unusual operating noise.
Provide sufficient service space.
Do NOT install the unit so that it is in contact with a ceiling or a wall, as this may
cause vibrations.
Choose a location where the operation noise or the hot/cold air discharged from
the unit will not disturb anyone and the location is selected according the
applicable legislation.
Provide sufficient space around the unit for servicing and air circulation.
Avoid areas where flammable gas or product might leak.
Install units, power cables and communication wiring at least 3 m away from
televisions or radios to prevent interference. Depending on the radio waves, a
distance of 3m may not be sufficient.
WARNING
Do NOT place objects below the indoor and/or outdoor unit that may get wet.
Otherwise condensation on the unit or refrigerant pipes, air filter dirt or drain
blockage may cause dripping, and objects under the unit may get dirty or damaged.
WARNING
The appliance shall be stored in a room without continuously operating ignition
sources (example: open flames, an operating gas appliance or an operating electric
heater).
6 | Unit installation
Installer reference guide
26
RXF20~42E5V1B+ARXF20~42E5V1B
R32 split series
4P519439-21V – 2022.10
WARNING
Make sure installation, servicing, maintenance and repair comply with instructions
from Daikin and with applicable legislation and are executed ONLY by authorised
persons.
6.1.1 Installation site requirements of the outdoor unit
INFORMATION
Also read the following requirements:
General installation site requirements. See the "General safety precautions"
chapter.
Refrigerant piping requirements (length, height difference). See further in this
"Preparation" chapter.
Mind the following spacing guidelines:
≤1200
>150
>150
>50
>300
>300
(mm)(mm)
a
b
b
a
a Air outlet
b Air inlet
NOTICE
Do NOT stack the units on each other.
Do NOT hang the unit on a ceiling.
Strong winds (≥18km/h) blowing against the outdoor unit’s air outlet causes short
circuit (suction of discharge air). This may result in:
deterioration of the operational capacity;
frequent frost acceleration in heating operation;
disruption of operation due to decrease of low pressure or increase of high
pressure;
a broken fan (if a strong wind blows continuously on the fan, it may start rotating
very fast, until it breaks).
It is recommended to install a baffle plate when the air outlet is exposed to wind.
It is recommended to install the outdoor unit with the air inlet facing the wall and
NOT directly exposed to the wind.
6 | Unit installation
Installer reference guide
27
RXF20~42E5V1B+ARXF20~42E5V1B
R32 split series
4P519439-21V – 2022.10
b
a
b
c
a Baffle plate
b Prevailing wind direction
c Air outlet
Do NOT install the unit in the following places:
Sound sensitive areas (e.g. near a bedroom), so that the operation noise will
cause no trouble.
Note: If the sound is measured under actual installation conditions, the
measured value might be higher than the sound pressure level mentioned in
Sound spectrum in the data book due to environmental noise and sound
reflections.
INFORMATION
The sound pressure level is less than 70dBA.
In places where a mineral oil mist, spray or vapour may be present in the
atmosphere. Plastic parts may deteriorate and fall off or cause water leakage.
It is NOT recommended to install the unit in the following places because it may
shorten the life of the unit:
Where the voltage fluctuates a lot
In vehicles or vessels
Where acidic or alkaline vapour is present
Seaside installation. Make sure the outdoor unit is NOT directly exposed to sea
winds. This is to prevent corrosion caused by high levels of salt in the air, which
might shorten the life of the unit.
Install the outdoor unit away from direct sea winds.
Example: Behind the building.
b
c
a
If the outdoor unit is exposed to direct sea winds, install a windbreaker.
Height of windbreaker≥1.5×height of outdoor unit
Mind the service space requirements when installing the windbreaker.
6 | Unit installation
Installer reference guide
28
RXF20~42E5V1B+ARXF20~42E5V1B
R32 split series
4P519439-21V – 2022.10
a
b
c
d
c
d
a Sea wind
b Building
c Outdoor unit
d Windbreaker
The outdoor unit is designed for outdoor installation only, and for ambient
temperatures ranging from –10 to 46°C in cooling mode and from –15 to 24°C in
heating mode. Unless otherwise specified in the operation manual of the
connected indoor unit.
6.1.2 Additional installation site requirements of the outdoor unit in cold climates
Protect the outdoor unit against direct snowfall and take care that the outdoor unit
is NEVER snowed up.
a
b
c
c
d
a Snow cover or shed
b Pedestal
c Prevailing wind direction
d Air outlet
In any case, provide at least 300 mm of free space below the unit. Additionally,
make sure the unit is positioned at least 100 mm above the maximum expected
level of snow. See "6.3Mounting the outdoor unit"[429] for more details.
In heavy snowfall areas it is very important to select an installation site where the
snow will NOT affect the unit. If lateral snowfall is possible, make sure that the heat
exchanger coil is NOT affected by the snow. If necessary, install a snow cover or
shed and a pedestal.
6 | Unit installation
Installer reference guide
29
RXF20~42E5V1B+ARXF20~42E5V1B
R32 split series
4P519439-21V – 2022.10
6.2 Opening the units
6.2.1 About opening the units
At certain times, you have to open the unit. Example:
When connecting the refrigerant piping
When connecting the electrical wiring
When maintaining or servicing the unit
DANGER: RISK OF ELECTROCUTION
Do NOT leave the unit unattended when the service cover is removed.
6.2.2 To open the outdoor unit
DANGER: RISK OF ELECTROCUTION
DANGER: RISK OF BURNING/SCALDING
2
1
2
6.3 Mounting the outdoor unit
6.3.1 About mounting the outdoor unit
When
The outdoor and indoor unit must be mounted before the refrigerant piping can be
connected.
Typical workflow
Mounting the outdoor unit typically consists of the following stages:
1 Providing the installation structure.
2 Installing the outdoor unit.
3 Providing drainage.
4 Preventing the unit from falling over.
5 Protecting the unit against snow and wind by installing a snow cover and baffle
plates. See "6.1Preparing the installation site"[425].
6 | Unit installation
Installer reference guide
30
RXF20~42E5V1B+ARXF20~42E5V1B
R32 split series
4P519439-21V – 2022.10
6.3.2 Precautions when mounting the outdoor unit
INFORMATION
Also read the precautions and requirements in the following chapters:
General safety precautions
Preparation
6.3.3 To provide the installation structure
Check the strength and level of the installation ground so that the unit will not
cause any operating vibration or noise.
Fix the unit securely by means of foundation bolts in accordance with the
foundation drawing.
Prepare 4 sets of M8 or M10 anchor bolts, nuts and washers (field supply).
20 mm
300
470
192
(mm)
192
a
a 100mm above expected level of snow
6.3.4 To install the outdoor unit
M8/M10
6 | Unit installation
Installer reference guide
31
RXF20~42E5V1B+ARXF20~42E5V1B
R32 split series
4P519439-21V – 2022.10
6.3.5 To provide drainage
Make sure that condensation water can be evacuated properly.
Install the unit on a base to make sure that there is proper drainage in order to
avoid ice accumulation.
Prepare a water drainage channel around the foundation to drain waste water
away from the unit.
Avoid drain water flowing over the footpath, so that it does NOT become slippery
in case of ambient freezing temperatures.
If you install the unit on a frame, install a waterproof plate within 150mm of the
bottom side of the unit in order to prevent water from getting into the unit and
to avoid drain water dripping (see the following figure).
NOTICE
If the unit is installed in a cold climate, take adequate measures so that the
evacuated condensate CANNOT freeze.
NOTICE
If the drain holes of the outdoor unit are blocked up by a mounting base or floor
surface, place additional foot bases ≤30mm under the outdoor unit's feet.
INFORMATION
For information on the available options, contact your dealer.
1 Use a drain plug for drainage.
2 Use a Ø16mm hose (field supply).
a
c
b
d
a Drain port
b Bottom frame
c Drain plug
d Hose (field supply)
6.3.6 To prevent the outdoor unit from falling over
In case the unit is installed in places where strong wind can tilt the unit, take
following measure:
1 Prepare 2 cables as indicated in the following illustration (field supply).
2 Place the 2 cables over the outdoor unit.
6 | Unit installation
Installer reference guide
32
RXF20~42E5V1B+ARXF20~42E5V1B
R32 split series
4P519439-21V – 2022.10
3 Insert a rubber sheet between the cables and the outdoor unit to prevent the
cables from scratching the paint (field supply).
4 Attach the ends of the cables.
5 Tighten the cables.
7 | Piping installation
Installer reference guide
33
RXF20~42E5V1B+ARXF20~42E5V1B
R32 split series
4P519439-21V – 2022.10
7 Piping installation
In this chapter
7.1 Preparing refrigerant piping................................................................................................................................................... 33
7.1.1 Refrigerant piping requirements ........................................................................................................................... 33
7.1.2 Refrigerant piping length and height difference ................................................................................................... 33
7.1.3 Refrigerant piping insulation.................................................................................................................................. 34
7.2 Connecting the refrigerant piping.......................................................................................................................................... 34
7.2.1 About connecting the refrigerant piping............................................................................................................... 34
7.2.2 Precautions when connecting the refrigerant piping............................................................................................ 34
7.2.3 Guidelines when connecting the refrigerant piping.............................................................................................. 36
7.2.4 Pipe bending guidelines ......................................................................................................................................... 36
7.2.5 To flare the pipe end.............................................................................................................................................. 36
7.2.6 Using the stop valve and service port.................................................................................................................... 37
7.2.7 To connect the refrigerant piping to the outdoor unit ......................................................................................... 38
7.3 Checking the refrigerant piping.............................................................................................................................................. 39
7.3.1 About checking the refrigerant piping................................................................................................................... 39
7.3.2 Precautions when checking the refrigerant piping ............................................................................................... 39
7.3.3 To check for leaks................................................................................................................................................... 40
7.3.4 To perform vacuum drying .................................................................................................................................... 40
7.4 Charging refrigerant ............................................................................................................................................................... 41
7.4.1 About charging refrigerant .................................................................................................................................... 41
7.4.2 About the refrigerant ............................................................................................................................................. 42
7.4.3 To determine the additional refrigerant amount.................................................................................................. 43
7.4.4 To determine the complete recharge amount...................................................................................................... 43
7.4.5 To charge additional refrigerant............................................................................................................................ 44
7.4.6 To fix the fluorinated greenhouse gases label....................................................................................................... 44
7.1 Preparing refrigerant piping
7.1.1 Refrigerant piping requirements
INFORMATION
Also read the precautions and requirements in the "2 General safety
precautions"[46].
Piping material: phosphoric acid deoxidised seamless copper
Piping diameter:
Liquid piping Ø6.4mm (1/4")
Gas piping Ø9.5mm (3/8")
Piping temper grade and thickness:
Outer diameter (Ø) Temper grade Thickness (t)
(a)
6.4mm (1/4") Annealed (O) ≥0.8mm
t
Ø
9.5mm (3/8") Annealed (O)
(a)
Depending on the applicable legislation and the maximum working pressure of the unit
(see "PS High" on the unit name plate), larger piping thickness might be required.
7.1.2 Refrigerant piping length and height difference
What? Distance
Maximum allowable pipe length 20m
7 | Piping installation
Installer reference guide
34
RXF20~42E5V1B+ARXF20~42E5V1B
R32 split series
4P519439-21V – 2022.10
What? Distance
Minimum allowable pipe length 1.5m
Maximum allowable height difference 12m
7.1.3 Refrigerant piping insulation
Use polyethylene foam as insulation material:
- with a heat transfer rate between 0.041 and 0.052 W/mK (0.035 and
0.045kcal/mh°C)
- with a heat resistance of at least 120°C
Insulation thickness
Pipe outer diameter (Ø
p
) Insulation inner diameter
i
)
Insulation thickness (t)
6.4mm (1/4") 8~10mm ≥10mm
9.5mm (3/8") 12~15mm
Ø
i
Ø
i
t
Ø
p
Ø
p
If the temperature is higher than 30°C and the humidity is higher than RH80%, the
thickness of the insulation materials should be at least 20 mm to prevent
condensation on the surface of the insulation.
7.2 Connecting the refrigerant piping
7.2.1 About connecting the refrigerant piping
Before connecting the refrigerant piping
Make sure the outdoor and indoor unit are mounted.
Typical workflow
Connecting the refrigerant piping involves:
Connecting the refrigerant piping to the indoor unit
Connecting the refrigerant piping to the outdoor unit
Insulating the refrigerant piping
Keeping in mind the guidelines for:
- Pipe bending
- Flaring pipe ends
- Using the stop valves
7.2.2 Precautions when connecting the refrigerant piping
DANGER: RISK OF BURNING/SCALDING
7 | Piping installation
Installer reference guide
35
RXF20~42E5V1B+ARXF20~42E5V1B
R32 split series
4P519439-21V – 2022.10
NOTICE
Use the flare nut fixed to the main unit.
To prevent gas leakage, apply refrigeration oil only to the inside of the flare. Use
refrigeration oil for R32 (Example: FW68DA).
Do NOT reuse joints.
NOTICE
Do NOT use mineral oil on flared part.
Do NOT reuse piping from previous installations.
NEVER install a drier to this R32 unit to guarantee its lifetime. The drying material
may dissolve and damage the system.
NOTICE
Take the following precautions on refrigerant piping into account:
Avoid anything but the designated refrigerant to get mixed into the refrigerant
cycle (e.g. air).
Only use R32 when adding refrigerant.
Only use installation tools (e.g. manifold gauge set) that are exclusively used for
R32 installations to withstand the pressure and to prevent foreign materials (e.g.
mineral oils and moisture) from mixing into the system.
Install the piping so that the flare is NOT subjected to mechanical stress.
Do NOT leave pipes unattended at the site. If the installation is NOT done within 1
day, protect the piping as described in the following table to prevent dirt, liquid
or dust from entering the piping.
Use caution when passing copper tubes through walls (see figure below).
Unit Installation period Protection method
Outdoor unit >1month Pinch the pipe
<1month Pinch or tape the pipe
Indoor unit Regardless of the period
NOTICE
Do NOT open the refrigerant stop valve before checking the refrigerant piping. When
you need to charge additional refrigerant it is recommended to open the refrigerant
stop valve after charging.
WARNING
Connect the refrigerant piping securely before running the compressor. If the
refrigerant piping is NOT connected and the stop valve is open when the compressor
is run, air will be sucked in. This will cause abnormal pressure in the refrigeration
cycle, which may result in equipment damage and even injury.
7 | Piping installation
Installer reference guide
36
RXF20~42E5V1B+ARXF20~42E5V1B
R32 split series
4P519439-21V – 2022.10
7.2.3 Guidelines when connecting the refrigerant piping
Take the following guidelines into account when connecting pipes:
Coat the flare inner surface with ether oil or ester oil when connecting a flare
nut. Tighten 3 or 4 turns by hand, before tightening firmly.
ALWAYS use 2 wrenches together when loosening a flare nut.
ALWAYS use a spanner and torque wrench together to tighten the flare nut when
connecting the piping. This to prevent nut cracking and leaks.
a
b
c
d
a Torque wrench
b Spanner
c Piping union
d Flare nut
Piping size (mm) Tightening torque
(N•m)
Flare dimensions
(A) (mm)
Flare shape (mm)
Ø6.4 15~17 8.7~9.1
R=
0.4~0.8
±2
45°
90°
±2
ØA
Ø9.5 33~39 12.8~13.2
7.2.4 Pipe bending guidelines
Use a pipe bender for bending. All pipe bends should be as gentle as possible
(bending radius should be 30~40 mm or larger).
7.2.5 To flare the pipe end
CAUTION
Incomplete flaring may cause refrigerant gas leakage.
Do NOT re-use flares. Use new flares to prevent refrigerant gas leakage.
Use flare nuts that are included with the unit. Using different flare nuts may
cause refrigerant gas leakage.
1 Cut the pipe end with a pipe cutter.
2 Remove burrs with the cut surface facing down so that the chips do NOT enter
the pipe.
a b
a Cut exactly at right angles.
b Remove burrs.
3 Remove the flare nut from the stop valve and put the flare nut on the pipe.
7 | Piping installation
Installer reference guide
37
RXF20~42E5V1B+ARXF20~42E5V1B
R32 split series
4P519439-21V – 2022.10
4 Flare the pipe. Set exactly at the position as shown in the following figure.
A
Flare tool for R32
(clutch type)
Conventional flare tool
Clutch type
(Ridgid-type)
Wing nut type
(Imperial-type)
A 0~0.5mm 1.0~1.5mm 1.5~2.0mm
5 Check that the flaring is properly made.
a b
c
a Flare’s inner surface MUST be flawless.
b The pipe end MUST be evenly flared in a perfect circle.
c Make sure the flare nut is fitted.
7.2.6 Using the stop valve and service port
CAUTION
Do NOT open the valves before flaring is complete. This would cause refrigerant gas
leakage.
To handle the stop valve
Take the following guidelines into account:
The stop valves are factory closed.
The following figure shows the stop valve parts required when handling the
valve.
c
d
a
b
a Service port and service port cap
b Valve stem
c Field piping connection
d Stem cap
Keep both stop valves open during operation.
Do NOT apply excessive force to the valve stem. Doing so may break the valve
body.
ALWAYS make sure to secure the stop valve with a spanner, then loosen or
tighten the flare nut with a torque wrench. Do NOT place the spanner on the
stem cap, as this could cause a refrigerant leak.
a
b
7 | Piping installation
Installer reference guide
38
RXF20~42E5V1B+ARXF20~42E5V1B
R32 split series
4P519439-21V – 2022.10
a Spanner
b Torque wrench
When it is expected that the operating pressure will be low (e.g. when cooling
will be performed while the outside air temperature is low), sufficiently seal the
flare nut in the stop valve on the gas line with silicon sealant to prevent freezing.
Silicon sealant, make sure there is no gap.
To open/close the stop valve
1 Remove the stop valve cover.
2 Insert a hexagon wrench (liquid side: 4 mm, gas side: 4 mm) into the valve
stem and turn the valve stem:
Counterclockwise to open
Clockwise to close
3 When the stop valve CANNOT be turned any further, stop turning.
4 Install the stop valve cover.
Result: The valve is now open/closed.
To handle the stem cap
The stem cap is sealed where indicated with the arrow. Do NOT damage it.
After handling the stop valve, tighten the stem cap, and check for refrigerant
leaks.
Item Tightening torque (N∙m)
Stem cap, liquid side 21.6~27.4
Stem cap, gas side 21.6~27.4
To handle the service cap
ALWAYS use a charge hose equipped with a valve depressor pin, since the service
port is a Schrader type valve.
After handling the service port, tighten the service port cap, and check for
refrigerant leaks.
Item Tightening torque (N∙m)
Service port cap 10.8~14.7
7.2.7 To connect the refrigerant piping to the outdoor unit
Piping length. Keep field piping as short as possible.
Piping protection. Protect the field piping against physical damage.
7 | Piping installation
Installer reference guide
39
RXF20~42E5V1B+ARXF20~42E5V1B
R32 split series
4P519439-21V – 2022.10
1 Connect the liquid refrigerant connection from the indoor unit to the liquid
stop valve of the outdoor unit.
a
c b
a Liquid stop valve
b Gas stop valve
c Service port
2 Connect the gas refrigerant connection from the indoor unit to the gas stop
valve of the outdoor unit.
NOTICE
It is recommended that the refrigerant piping between indoor and outdoor unit is
installed in a ducting or the refrigerant piping is wrapped with finishing tape.
7.3 Checking the refrigerant piping
7.3.1 About checking the refrigerant piping
The outdoor unit's internal refrigerant piping has been factory tested for leaks. You
only have to check the outdoor unit's external refrigerant piping.
Before checking the refrigerant piping
Make sure the refrigerant piping is connected between the outdoor unit and the
indoor unit.
Typical workflow
Checking the refrigerant piping typically consists of the following stages:
1 Checking for leaks in the refrigerant piping.
2 Performing vacuum drying to remove all moisture, air or nitrogen from the
refrigerant piping.
If there is a possibility of moisture being present in the refrigerant piping (for
example, water may have entered the piping), first carry out the vacuum drying
procedure below until all moisture has been removed.
7.3.2 Precautions when checking the refrigerant piping
INFORMATION
Also read the precautions and requirements in the following chapters:
General safety precautions
Preparation
NOTICE
Use a 2-stage vacuum pump with a non-return valve that can evacuate to a gauge
pressure of −⁠100.7kPa (−⁠1.007bar)(5Torr absolute). Make sure the pump oil does
not flow oppositely into the system while the pump is not working.
7 | Piping installation
Installer reference guide
40
RXF20~42E5V1B+ARXF20~42E5V1B
R32 split series
4P519439-21V – 2022.10
NOTICE
Use this vacuum pump for R32 exclusively. Using the same pump for other
refrigerants may damage the pump and the unit.
NOTICE
Connect the vacuum pump to the service port of the gas stop valve.
Make sure that the gas stop valve and liquid stop valve are firmly closed before
performing the leak test or vacuum drying.
7.3.3 To check for leaks
NOTICE
Do NOT exceed the unit's maximum working pressure (see "PS High" on the unit
name plate).
NOTICE
ALWAYS use a recommended bubble test solution from your wholesaler.
NEVER use soap water:
Soap water may cause cracking of components, such as flare nuts or stop valve
caps.
Soap water may contain salt, which absorbs moisture that will freeze when the
piping gets cold.
Soap water contains ammonia which may lead to corrosion of flared joints
(between the brass flare nut and the copper flare).
1 Charge the system with nitrogen gas up to a gauge pressure of at least
200kPa (2bar). It is recommended to pressurize to 3000kPa (30bar) in order
to detect small leaks.
2 Check for leaks by applying the bubble test solution to all connections.
3 Discharge all nitrogen gas.
7.3.4 To perform vacuum drying
Connect the vacuum pump and manifold as follows:
i
h
j
a
b
c
h
k
d
f
f
e
g
a Low pressure gauge
b Gauge manifold
c High pressure gauge
d Low-pressure valve (Lo)
e High-pressure valve (Hi)
7 | Piping installation
Installer reference guide
41
RXF20~42E5V1B+ARXF20~42E5V1B
R32 split series
4P519439-21V – 2022.10
f Charging hoses
g Vacuum pump
h Valve caps
i Service port
j Gas stop valve
k Liquid stop valve
1 Vacuum the system until the pressure on the manifold indicates −0.1 MPa
(−1bar).
2 Leave as is for 4-5minutes and check the pressure:
If the pressure… Then…
Does not change There is no moisture in the system.
This procedure is finished.
Increases There is moisture in the system. Go
to the next step.
3 Vacuum the system for at least 2hours to a manifold pressure of −0.1MPa
(−1bar).
4 After turning the pump OFF, check the pressure for at least 1hour.
5 If you do NOT reach the target vacuum or CANNOT maintain the vacuum for
1hour, do the following:
Check for leaks again.
Perform vacuum drying again.
NOTICE
Make sure to open the stop valves after installing the refrigerant piping and
performing vacuum drying. Running the system with the stop valves closed may
break the compressor.
INFORMATION
After opening the stop valve, it is possible that the pressure in the refrigerant piping
does NOT increase. This might be caused by e.g. the closed state of the expansion
valve in the outdoor unit circuit, but does NOT present any problem for correct
operation of the unit.
7.4 Charging refrigerant
7.4.1 About charging refrigerant
The outdoor unit is factory charged with refrigerant, but in some cases the
following might be necessary:
What When
Charging additional refrigerant When the total liquid piping length is
more than specified (see later).
Completely recharging refrigerant Example:
When relocating the system.
After a leak.
Charging additional refrigerant
Before charging additional refrigerant, make sure the outdoor unit's external
refrigerant piping is checked (leak test, vacuum drying).
7 | Piping installation
Installer reference guide
42
RXF20~42E5V1B+ARXF20~42E5V1B
R32 split series
4P519439-21V – 2022.10
INFORMATION
Depending on the units and/or the installation conditions, it might be necessary to
connect electrical wiring before you can charge refrigerant.
Typical workflow – Charging additional refrigerant typically consists of the following
stages:
1 Determining if and how much you have to charge additionally.
2 If necessary, charging additional refrigerant.
3 Filling in the fluorinated greenhouse gases label, and fixing it to the inside of
the outdoor unit.
Completely recharging refrigerant
Before completely recharging refrigerant, make sure the following is done:
1 All refrigerant is recovered from the system.
2 The outdoor unit's external refrigerant piping is checked (leak test, vacuum
drying).
3 Vacuum drying on the outdoor unit's internal refrigerant piping is performed.
NOTICE
Before completely recharging, perform vacuum drying on the outdoor unit's internal
refrigerant piping as well.
Typical workflow Completely recharging refrigerant typically consists of the
following stages:
1 Determining how much refrigerant to charge.
2 Charging refrigerant.
3 Filling in the fluorinated greenhouse gases label, and fixing it to the inside of
the outdoor unit.
7.4.2 About the refrigerant
This product contains fluorinated greenhouse gases. Do NOT vent gases into the
atmosphere.
Refrigerant type: R32
Global warming potential (GWP) value: 675
Periodical inspections for refrigerant leaks may be required depending on the
applicable legislation. Contact your installer for more information.
WARNING: MILDLY FLAMMABLE MATERIAL
The refrigerant inside this unit is mildly flammable.
7 | Piping installation
Installer reference guide
43
RXF20~42E5V1B+ARXF20~42E5V1B
R32 split series
4P519439-21V – 2022.10
WARNING
The refrigerant inside the unit is mildly flammable, but normally does NOT leak. If
the refrigerant leaks in the room and comes in contact with fire from a burner, a
heater, or a cooker, this may result in fire, or the formation of a harmful gas.
Turn OFF any combustible heating devices, ventilate the room, and contact the
dealer where you purchased the unit.
Do NOT use the unit until a service person confirms that the part from which the
refrigerant leaked has been repaired.
WARNING
The appliance shall be stored in a room without continuously operating ignition
sources (example: open flames, an operating gas appliance or an operating electric
heater).
WARNING
Do NOT pierce or burn refrigerant cycle parts.
Do NOT use cleaning materials or means to accelerate the defrosting process
other than those recommended by the manufacturer.
Be aware that the refrigerant inside the system is odourless.
NOTICE
Applicable legislation on fluorinated greenhouse gases requires that the refrigerant
charge of the unit is indicated both in weight and CO
2
equivalent.
Formula to calculate the quantity in CO
2
equivalent tonnes: GWP value of the
refrigerant × total refrigerant charge [in kg]/1000
Contact your installer for more information.
7.4.3 To determine the additional refrigerant amount
If the total liquid piping
length is…
Then…
≤10m Do NOT add additional refrigerant.
>10m R=(total length (m) of liquid piping⁠–⁠10m)×0.020
R=Additional charge (kg) (rounded in units of
0.01kg)
INFORMATION
Piping length is the one-way length of liquid piping.
7.4.4 To determine the complete recharge amount
INFORMATION
If a complete recharge is necessary, the total refrigerant charge is: the factory
refrigerant charge (see unit name plate) + the determined additional amount.
7 | Piping installation
Installer reference guide
44
RXF20~42E5V1B+ARXF20~42E5V1B
R32 split series
4P519439-21V – 2022.10
7.4.5 To charge additional refrigerant
WARNING
Only use R32 as refrigerant. Other substances may cause explosions and
accidents.
R32 contains fluorinated greenhouse gases. Its global warming potential (GWP)
value is 675. Do NOT vent these gases into the atmosphere.
When charging refrigerant, ALWAYS use protective gloves and safety glasses.
NOTICE
To avoid compressor breakdown, do NOT charge more than the specified amount of
refrigerant.
Prerequisite: Before charging refrigerant, make sure the refrigerant piping is
connected and checked (leak test and vacuum drying).
1 Connect the refrigerant cylinder to the service port.
2 Charge the additional refrigerant amount.
3 Open the gas stop valve.
If pump down is needed in case of dismantling or relocating the system, see
"14.2To pump down"[459] for more details.
7.4.6 To fix the fluorinated greenhouse gases label
1 Fill in the label as follows:
b
Contains fluorinated greenhouse gases
2
1
1
1
2
2
kg
tCO
2
eq
GWP × kg
1000
=
=
+
kg
=
kg
=
GWP: XXX
RXXX
a
f
c
d
e
a If a multilingual fluorinated greenhouse gases label is delivered with the unit (see
accessories), peel off the applicable language and stick it on top of a.
b Factory refrigerant charge: see unit name plate
c Additional refrigerant amount charged
d Total refrigerant charge
e Quantity of fluorinated greenhouse gases of the total refrigerant charge
expressed as tonnes CO
2
equivalent.
f GWP = Global Warming Potential
NOTICE
Applicable legislation on fluorinated greenhouse gases requires that the refrigerant
charge of the unit is indicated both in weight and CO
2
equivalent.
Formula to calculate the quantity in CO
2
equivalent tonnes: GWP value of the
refrigerant × total refrigerant charge [in kg] / 1000
Use the GWP value mentioned on the refrigerant charge label.
2 Fix the label on the inside of the outdoor unit near the gas and liquid stop
valves.
8 | Electrical installation
Installer reference guide
45
RXF20~42E5V1B+ARXF20~42E5V1B
R32 split series
4P519439-21V – 2022.10
8 Electrical installation
In this chapter
8.1 Preparing electrical wiring...................................................................................................................................................... 45
8.1.1 About preparing electrical wiring .......................................................................................................................... 45
8.2 Connecting the electrical wiring............................................................................................................................................. 46
8.2.1 About connecting the electrical wiring.................................................................................................................. 46
8.2.2 Precautions when connecting the electrical wiring .............................................................................................. 46
8.2.3 Guidelines when connecting the electrical wiring ................................................................................................ 47
8.2.4 Specifications of standard wiring components ..................................................................................................... 48
8.2.5 To connect the electrical wiring to the outdoor unit ............................................................................................ 48
8.1 Preparing electrical wiring
8.1.1 About preparing electrical wiring
INFORMATION
Also read the precautions and requirements in the "2 General safety
precautions"[46].
INFORMATION
Also read "8.2.4Specifications of standard wiring components"[448].
WARNING
If the power supply has a missing or wrong N-phase, equipment might break
down.
Establish proper earthing. Do NOT earth the unit to a utility pipe, surge absorber,
or telephone earth. Incomplete earthing may cause electrical shock.
Install the required fuses or circuit breakers.
Secure the electrical wiring with cable ties so that the cables do NOT come in
contact with sharp edges or piping, particularly on the high-pressure side.
Do NOT use taped wires, extension cords, or connections from a star system.
They can cause overheating, electrical shock or fire.
Do NOT install a phase advancing capacitor, because this unit is equipped with an
inverter. A phase advancing capacitor will reduce performance and may cause
accidents.
WARNING
All wiring MUST be performed by an authorised electrician and MUST comply
with the applicable national wiring regulation.
Make electrical connections to the fixed wiring.
All components procured on-site and all electrical construction MUST comply
with the applicable legislation.
WARNING
ALWAYS use multicore cable for power supply cables.
8 | Electrical installation
Installer reference guide
46
RXF20~42E5V1B+ARXF20~42E5V1B
R32 split series
4P519439-21V – 2022.10
8.2 Connecting the electrical wiring
8.2.1 About connecting the electrical wiring
Typical workflow
Connecting the electrical wiring typically consists of the following stages:
1 Making sure the power supply system complies with the electrical
specifications of the units.
2 Connecting the electrical wiring to the outdoor unit.
3 Connecting the electrical wiring to the indoor unit.
4 Connecting the main power supply.
8.2.2 Precautions when connecting the electrical wiring
DANGER: RISK OF ELECTROCUTION
WARNING
All wiring MUST be performed by an authorised electrician and MUST comply
with the applicable national wiring regulation.
Make electrical connections to the fixed wiring.
All components procured on-site and all electrical construction MUST comply
with the applicable legislation.
WARNING
ALWAYS use multicore cable for power supply cables.
WARNING
If the supply cord is damaged, it MUST be replaced by the manufacturer, its service
agent or similarly qualified persons in order to avoid a hazard.
WARNING
Do NOT connect the power supply to the indoor unit. This could result in electrical
shock or fire.
WARNING
Do NOT use locally purchased electrical parts inside the product.
Do NOT branch the power supply for the drain pump, etc. from the terminal
block. This could result in electrical shock or fire.
WARNING
Keep the interconnection wiring away from copper pipes without thermal insulation
as such pipes will be very hot.
8 | Electrical installation
Installer reference guide
47
RXF20~42E5V1B+ARXF20~42E5V1B
R32 split series
4P519439-21V – 2022.10
INFORMATION
Also read the precautions and requirements in the following chapters:
General safety precautions
Preparation
8.2.3 Guidelines when connecting the electrical wiring
Keep the following in mind:
NOTICE
We recommend using solid (single-core) wires. If stranded wires are used, twist the
conductor to consolidate the end or twist the conductor to consolidate the end in
combination with the usage of a round crimp-style terminal on the end of the
conductor.
To prepare stranded conductor wire for installation
Method 1: Twisting conductor
1 Strip insulation (20 mm) from the wires.
2 Twist the end of the conductor to create a "solid-like" connection.
Method 2: Using round crimp-style terminal
1 Strip insulation from wires and twist the end of each wire.
2 Install a round crimp-style terminal on the end of the wire. Place the round
crimp-style terminal on the wire up to the covered part and fasten the
terminal with the appropriate tool.
Use the following methods for installing wires:
Wire type Installation method
Single-core wire
Or
Stranded conductor wire
twisted to "solid-like"
connection
c b
c
aa
A
AA´
a Curled wire (single-core or twisted stranded
conductor wire)
b Screw
c Flat washer
8 | Electrical installation
Installer reference guide
48
RXF20~42E5V1B+ARXF20~42E5V1B
R32 split series
4P519439-21V – 2022.10
Wire type Installation method
Stranded conductor wire
with round crimp-style
terminal
c b ba c
a
B
B
a Terminal
b Screw
c Flat washer
Allowed
NOT allowed
Tightening torques
Item Tightening torque (N•m)
M4 (X1M) 1.2~1.5
M4 (earth)
The earth wire between the wire retainer and the terminal must be longer than
the other wires.
1-3
8.2.4 Specifications of standard wiring components
Component
Power supply cable Voltage 220~240V
Phase 1~
Frequency 50Hz
Wire sizes MUST comply with applicable
legislation
Interconnection cable (indoor↔outdoor) 4-core cable ≥1.5 mm² and
applicable for 220~240 V
Recommended field fuse 16A
Earth leakage circuit breaker MUST comply with applicable
legislation
8.2.5 To connect the electrical wiring to the outdoor unit
1 Remove the service cover. See "6.2.2To open the outdoor unit"[429].
2 Strip insulation (20mm) from the wires.
a b
a Strip wire end to this point
b An excessive strip length may cause electrical shock or leakage
3 Open the wire clamp.
8 | Electrical installation
Installer reference guide
49
RXF20~42E5V1B+ARXF20~42E5V1B
R32 split series
4P519439-21V – 2022.10
4 Connect the interconnection cable and power supply as follows:
f
50 Hz
220-240 V
a b
c d e
a Interconnection cable
b Power supply cable
c Circuit breaker
d Residual current device
e Power supply
f Earth
5 Tighten the terminal screws securely. We recommend using a Phillips
screwdriver.
9 | Finishing the outdoor unit installation
Installer reference guide
50
RXF20~42E5V1B+ARXF20~42E5V1B
R32 split series
4P519439-21V – 2022.10
9 Finishing the outdoor unit installation
9.1 To finish the outdoor unit installation
NOTICE
It is recommended that the refrigerant piping between indoor and outdoor unit is
installed in a ducting or the refrigerant piping is wrapped with finishing tape.
1 Insulate and fix the refrigerant piping and cables as follows:
g
b
a
f
e
cd
a Gas pipe
b Gas pipe insulation
c Interconnection cable
d Field wiring (if applicable)
e Liquid pipe
f Liquid pipe insulation
g Finishing tape
2 Install the service cover.
9.2 To close the outdoor unit
NOTICE
When closing the outdoor unit cover, make sure that the tightening torque does NOT
exceed 1.3N•m.
2
1
1
10 | Commissioning
Installer reference guide
51
RXF20~42E5V1B+ARXF20~42E5V1B
R32 split series
4P519439-21V – 2022.10
10 Commissioning
10.1 Overview: Commissioning
This chapter describes what you have to do and know to commission the system
after it is installed.
Typical workflow
Commissioning typically consists of the following stages:
1 Checking the "Checklist before commissioning".
2 Performing a test run for the system.
10.2 Precautions when commissioning
DANGER: RISK OF ELECTROCUTION
DANGER: RISK OF BURNING/SCALDING
CAUTION
Do NOT perform the test operation while working on the indoor units.
When performing the test operation, NOT ONLY the outdoor unit, but the connected
indoor unit will operate as well. Working on an indoor unit while performing a test
operation is dangerous.
CAUTION
Do NOT insert fingers, rods or other objects into the air inlet or outlet. Do NOT
remove the fan guard. When the fan is rotating at high speed, it will cause injury.
NOTICE
Turn ON the power 6 hours before operation in order to have power running to the
crankcase heater and to protect the compressor.
During test operation, the outdoor unit and the indoor units will start up. Make
sure that the preparations of all indoor units are finished (field piping, electrical
wiring, air purge, ...). See installation manual of the indoor units for details.
10.3 Checklist before commissioning
1 After the installation of the unit, check the items listed below.
2 Close the unit.
3 Power up the unit.
The indoor unit is properly mounted.
10 | Commissioning
Installer reference guide
52
RXF20~42E5V1B+ARXF20~42E5V1B
R32 split series
4P519439-21V – 2022.10
The outdoor unit is properly mounted.
The system is properly earthed and the earth terminals are tightened.
The power supply voltage matches the voltage on the identification label of the unit.
There are NO loose connections or damaged electrical components in the switchbox.
There are NO damaged components or squeezed pipes on the inside of the indoor and
outdoor units.
There are NO refrigerant leaks.
The refrigerant pipes (gas and liquid) are thermally insulated.
The correct pipe size is installed and the pipes are properly insulated.
The stop valves (gas and liquid) on the outdoor unit are fully open.
The following field wiring has been carried out according to this document and the
applicable legislation between the outdoor unit and the indoor unit.
Drainage
Make sure drainage flows smoothly.
Possible consequence: Condensate water might drip.
The indoor unit receives the signals of the user interface.
The specified wires are used for the interconnection cable.
The fuses, circuit breakers, or locally installed protection devices are installed according to
this document, and have NOT been bypassed.
10.4 Checklist during commissioning
To perform an air purge.
To perform a test run.
10.5 To perform a test run
Prerequisite: Power supply MUST be in the specified range.
Prerequisite: Test run may be performed in cooling or heating mode.
Prerequisite: Test run should be performed in accordance with the operation
manual of the indoor unit to make sure that all functions and parts are working
properly.
1 In cooling mode, select the lowest programmable temperature. In heating
mode, select the highest programmable temperature. Test run can be
disabled if necessary.
2 When the test run is finished, set the temperature to a normal level. In cooling
mode: 26~28°C, in heating mode: 20~24°C.
3 The system stops operating 3minutes after the unit is turned OFF.
10 | Commissioning
Installer reference guide
53
RXF20~42E5V1B+ARXF20~42E5V1B
R32 split series
4P519439-21V – 2022.10
INFORMATION
Even if the unit is turned OFF, it consumes electricity.
When the power turns back on after a power break, the previously selected
mode will be resumed.
10.6 Starting up the outdoor unit
See the indoor unit installation manual for configuration and commissioning of the
system.
11 | Hand-over to the user
Installer reference guide
54
RXF20~42E5V1B+ARXF20~42E5V1B
R32 split series
4P519439-21V – 2022.10
11 Hand-over to the user
Once the test run is finished and the unit operates properly, make sure the
following is clear for the user:
Make sure that the user has the printed documentation and ask him/her to keep
it for future reference. Inform the user that he can find the complete
documentation at the URL mentioned earlier in this manual.
Explain the user how to properly operate the system and what to do in case of
problems.
Show the user what to do for the maintenance of the unit.
Explain the user about energy saving tips as described in the operation manual.
13 | Troubleshooting
Installer reference guide
57
RXF20~42E5V1B+ARXF20~42E5V1B
R32 split series
4P519439-21V – 2022.10
13 Troubleshooting
13.1 Overview: Troubleshooting
This chapter describes what you have to do in case of problems.
It contains information about solving problems based on symptoms.
Before troubleshooting
Carry out a thorough visual inspection of the unit and look for obvious defects such
as loose connections or defective wiring.
13.2 Precautions when troubleshooting
DANGER: RISK OF ELECTROCUTION
DANGER: RISK OF BURNING/SCALDING
WARNING
When carrying out an inspection on the switch box of the unit, ALWAYS make
sure that the unit is disconnected from the mains. Turn off the respective circuit
breaker.
When a safety device was activated, stop the unit and find out why the safety
device was activated before resetting it. NEVER shunt safety devices or change
their values to a value other than the factory default setting. If you are unable to
find the cause of the problem, call your dealer.
WARNING
Prevent hazards due to inadvertent resetting of the thermal cut-out: power to this
appliance MUST NOT be supplied through an external switching device, such as a
timer, or connected to a circuit that is regularly turned ON and OFF by the utility.
13.3 Solving problems based on symptoms
13.3.1 Symptom: Indoor units fall, vibrate or make noise
Possible causes Corrective action
The indoor units are NOT installed
securely.
Install the indoor units securely.
13 | Troubleshooting
Installer reference guide
58
RXF20~42E5V1B+ARXF20~42E5V1B
R32 split series
4P519439-21V – 2022.10
13.3.2 Symptom: The unit is NOT heating or cooling as expected
Possible causes Corrective action
Wrong connection of the electrical
wires
Connect the electrical wires correctly.
Gas leakage Check for gas leakage.
13.3.3 Symptom: Water leakage
Possible causes Corrective action
Incomplete thermal insulation (gas and
liquid piping, indoor portions of the
drain hose extension).
Make sure the thermal insulation of the
piping and the drain hose is complete.
Improperly connected drainage. Secure the drainage.
13.3.4 Symptom: Electrical leakage
Possible causes Corrective action
The unit is NOT earthed correctly. Check and correct the connection of the
earth wiring.
13.3.5 Symptom: Unit does NOT function or burn damage
Possible causes Corrective action
The wiring was NOT performed in
accordance with the specifications.
Correct the wiring.
14 | Disposal
Installer reference guide
59
RXF20~42E5V1B+ARXF20~42E5V1B
R32 split series
4P519439-21V – 2022.10
14 Disposal
NOTICE
Do NOT try to dismantle the system yourself: dismantling of the system, treatment of
the refrigerant, oil and other parts MUST comply with applicable legislation. Units
MUST be treated at a specialised treatment facility for reuse, recycling and recovery.
Units are marked with the following symbol:
This means that electrical and electronic products may NOT be mixed with
unsorted household waste. Do NOT try to dismantle the system yourself:
dismantling the system, treatment of the refrigerant, of oil and of other parts
MUST be done by an authorised installer and MUST comply with applicable
legislation.
Units MUST be treated at a specialised treatment facility for reuse, recycling and
recovery. By ensuring this product is disposed of correctly, you will help to
prevent potential negative consequences for the environment and human
health. For more information, contact your installer or local authority.
14.1 Overview: Disposal
Typical workflow
Disposing of the system typically consists of the following stages:
1 Pumping down the system.
2 Bringing the system to a specialized treatment facility.
INFORMATION
For more details, see the service manual.
14.2 To pump down
DANGER: RISK OF EXPLOSION
Pump down – Refrigerant leakage. If you want to pump down the system, and there
is a leak in the refrigerant circuit:
Do NOT use the unit's automatic pump down function, with which you can collect
all refrigerant from the system into the outdoor unit. Possible consequence: Self-
combustion and explosion of the compressor because of air going into the
operating compressor.
Use a separate recovery system so that the unit's compressor does NOT have to
operate.
14 | Disposal
Installer reference guide
60
RXF20~42E5V1B+ARXF20~42E5V1B
R32 split series
4P519439-21V – 2022.10
NOTICE
During pump down operation, stop the compressor before removing the refrigerant
piping. If the compressor is still running and the stop valve is open during pump
down, air will be sucked into the system. Compressor breakdown or damage to the
system can result due to abnormal pressure in the refrigerant cycle.
Pump down operation will extract all refrigerant from the system into the outdoor
unit.
1 Remove the valve cap from the liquid stop valve and the gas stop valve.
2 Carry out forced cooling. See "14.3To start and stop forced cooling"[460].
3 After 5 to 10minutes (after only 1 or 2minutes in case of very low ambient
temperatures (<−10°C)), close the liquid stop valve with a hexagonal wrench.
4 Check on the manifold if the vacuum is reached.
5 After 2-3minutes, close the gas stop valve and stop forced cooling.
c
b
e
d
d
a
a Gas stop valve
b Closing direction
c Hexagonal wrench
d Valve cap
e Liquid stop valve
14.3 To start and stop forced cooling
There are 2methods to perform forced cooling.
Method 1. Using the indoor unit ON/OFF switch (if present on the indoor unit).
Method 2. Using the indoor unit user interface.
14.3.1 To start and stop forced cooling using the indoor unit ON/OFF switch
1 Press the ON/OFF switch for at least 5seconds.
Result: Operation will start.
INFORMATION
Forced cooling stops automatically after 15minutes.
2 To stop operation sooner, press the ON/OFF switch.
14.3.2 To start and stop forced cooling using the indoor unit user interface
1 Set the operation mode to cooling. Refer to "To perform a test run" in the
installation manual of the indoor unit.
15 | Technical data
Installer reference guide
62
RXF20~42E5V1B+ARXF20~42E5V1B
R32 split series
4P519439-21V – 2022.10
15.1 Wiring diagram
,
A
INDOOR
OUTDOOR
For applied parts and numbering, refer to the wiring diagram on the unit. Part numbering is by Arabic numbers in ascending order for each part
and is represented in the overview below by symbol “*” in the part code.
Unified Wiring Diagram Legend
: CIRCUIT BREAKER
: CONNECTION
: CONNECTOR
: EARTH
: FIELD WIRING
: FUSE
: INDOOR UNIT
: OUTDOOR UNIT
: PROTECTIVE EARTH
: PROTECTIVE EARTH (SCREW)
: RECTIFIER
: RELAY CONNECTOR
: SHORT-CIRCUIT CONNECTOR
: TERMINAL
: TERMINAL STRIP
: WIRE CLAMP
WHT : WHITE
YLW : YELLOW
PNK : PINK
PRP, PPL : PURPLE
RED : RED
GRN : GREEN
GRY : GREY
ORG : ORANGE
BLK : BLACK
BLU : BLUE
BRN : BROWN
A*P : PRINTED CIRCUIT BOARD
BS* : PUSHBUTTON ON/OFF, OPERATION SWITCH
BZ, H*O : BUZZER
C* : CAPACITOR
AC*, CN*, E*, HA*, HE*, HL*, HN*, : CONNECTION, CONNECTOR
HR*, MR*_A, MR*_B, S*, U, V,
W, X*A, K*R_*
D*, V*D : DIODE
DB* : DIODE BRIDGE
DS* : DIP SWITCH
E*H : HEATER
F*U, FU*
(FOR CHARACTERISTICS,
: FUSE
REFER TO PCB INSIDE YOUR UNIT)
FG* : CONNECTOR (FRAME GROUND)
H* : HARNESS
H*P, LED*, V*L : PILOT LAMP, LIGHT EMITTING DIODE
HAP : LIGHT EMITTING DIODE (SERVICE MONITOR GREEN)
HIGH VOLTAGE : HIGH VOLTAGE
IES : INTELLIGENT EYE SENSOR
IPM* : INTELLIGENT POWER MODULE
K*R, KCR, KFR, KHuR, K*M : MAGNETIC RELAY
L : LIVE
L* : COIL
L*R : REACTOR
M* : STEPPER MOTOR
M*C : COMPRESSOR MOTOR
M*F : FAN MOTOR
M*P : DRAIN PUMP MOTOR
M*S : SWING MOTOR
MR*, MRCW*, MRM*, MRN* : MAGNETIC RELAY
N : NEUTRAL
n=*, N=* : NUMBER OF PASSES THROUGH FERRITE CORE
PAM : PULSE-AMPLITUDE MODULATION
PCB* : PRINTED CIRCUIT BOARD
PM* : POWER MODULE
PS : SWITCHING POWER SUPPLY
PTC* : THERMISTOR PTC
Q* : INSULATED GATE BIPOLAR TRANSISTOR
(IGBT)
Q*DI : EARTH LEAK CIRCUIT BREAKER
Q*L : OVERLOAD PROTECTOR
Q*M : THERMO SWITCH
R* : RESISTOR
R*T : THERMISTOR
RC : RECEIVER
S*C : LIMIT SWITCH
S*L : FLOAT SWITCH
S*NPH : PRESSURE SENSOR (HIGH)
S*NPL : PRESSURE SENSOR (LOW)
S*PH, HPS* : PRESSURE SWITCH (HIGH)
S*PL : PRESSURE SWITCH (LOW)
S*T : THERMOSTAT
S*RH : HUMIDITY SENSOR
S*W, SW* : OPERATION SWITCH
SA*, F1S : SURGE ARRESTOR
SR*, WLU : SIGNAL RECEIVER
SS* : SELECTOR SWITCH
SHEET METAL : TERMINAL STRIP FIXED PLATE
T*R : TRANSFORMER
TC, TRC : TRANSMITTER
V*, R*V : VARISTOR
V*R : DIODE BRIDGE
WRC : WIRELESS REMOTE CONTROLLER
X* : TERMINAL
X*M : TERMINAL STRIP (BLOCK)
Y*E : ELECTRONIC EXPANSION VALVE COIL
Y*R, Y*S : REVERSING SOLENOID VALVE COIL
Z*C : FERRITE CORE
ZF, Z*F : NOISE FILTER
DAIKIN ISITMA VE SOĞUTMA SİSTEMLERİ SAN.TİC. A.Ş.
İSTANBUL / TÜRKİYE
Tel: 0216 453 27 00
Faks: 0216 671 06 00
Çağrı Merkezi: 444 999 0
Web: www.daikin.com.tr
lsuyu Mahallesi, Fevzi Çakmak Caddesi, Burçak Sokak, No:20, 34848 Maltepe
4P519439-21V 2022.10
Copyright 2022 Daikin
Verantwortung für Energie und Umwelt

Produkspesifikasjoner

Merke: Daikin
Kategori: Ikke kategorisert
Modell: RXF25E5V1B

Trenger du hjelp?

Hvis du trenger hjelp med Daikin RXF25E5V1B still et spørsmål nedenfor, og andre brukere vil svare deg




Ikke kategorisert Daikin Manualer

Ikke kategorisert Manualer

Nyeste Ikke kategorisert Manualer