Growatt Export Limitation Guide
1. Inverter model
Inverter series list below support the export limitation function by add a Growatt meter:
Growatt 750-3000-S, Growatt 2500-5500MTL-S
Growatt 3000-6000TL3-S, Growatt 7000-11000TL3-S, Growatt 12000-15000TL3-S
Growatt 17000-25000TL3-S, Growatt 30000-50000TL3-S
Note:
1. Make sure inverter with the latest firmware version.
2. Single-phase inverter, make sure the inverter with RS485 communication port.
2. Meter selection
For export limitation function, only Growatt meter are approved.
1-phase meter is Growatt SPM, 3-phase meter is Growatt TPM, 1-phase meter is for single-phase
system export limitation, for 3-phase system, please use Growatt 3-phase meter.
3. Meter connection
Follow the guide of direction on the meter, follow the arrows on the meter, input side connect to
grid side, output connect to home load side, meter install between grid and load applications as
below picture.
4. Communication with inverter
Inverter and meter communication via RS485 communication port, connect meter RS485 to inverter
RS485 connector as below picture.
Note: check the RS485 ports define in the manual.
GROWATT NEW ENERGY TECHNOLOGY CO.,LTD
Building B, Jiayu Industrial Zone, #28 Guanghui Road,
Longteng Community, Shiyan, Baoan District,
Shenzhen, P.R. China
T + 86 755 2951 5888
F + 86 755 2747 2131
P.C. 518000
E info@ginverter.com
W www.growatt.com
W www.ginverter.com
Inverter and meter connection 1
(750-3000-S, 2500-5500MTL-S, 3-15KTL3-S)
Inverter and meter connection
(17-25KTL3-S, 30-50KTL3-S)
5. Configuration
Export limitation enable/disable
When enable this function, means zero export, no power export to grid.
1. Configure via ShineServer (Recommend)
If the inverter is monitored online by Growatt monitoring system, you can do the configuration via
ShineServer. Login your account, click into Setting below “My Photovoltaic device”, click the
“Inverter Setting” button, enter the setting page.
GROWATT NEW ENERGY TECHNOLOGY CO.,LTD
Building B, Jiayu Industrial Zone, #28 Guanghui Road,
Longteng Community, Shiyan, Baoan District,
Shenzhen, P.R. China
T + 86 755 2951 5888
F + 86 755 2747 2131
P.C. 518000
E info@ginverter.com
W www.growatt.com
W www.ginverter.com
Click advance set, select the register, and fill in 202 and value 1 as below picture, then fill in the
password and click save, to enable this setting.
Note: Please check with Growatt service engineer for the password.
2. Configure via ShineBus and Modbus Test
Local configure with laptop, use USB to RS232 cable connect the laptop to the inverter RS232 port,
and open the software to do the setting.
Note: Please ask Growatt service engineer for the software.
ShineBus setting the model value to enable the export limitation function.
Read the inverter information first, and record the model value.
Note:
a. COM number is the COM address of the USB of your laptop, you can check it in device
manager on your computer.
b. Inv Add is inverter address, the default value is 1.