Maintenance fire extinguishers
General information
This information contains a general guideline for maintaining your fire extinguishers. If you are using
fire extinguishers in a commercial environment, legislation and insurance requirements may apply.
Please check with your local authorities to make sure you comply with all necessary rules and
regulations. The information in this document is general information that may not cover all situations
that may occur during maintenance.
European countries these qualified maintenances companies and the guidelines they follow are
identified in different ways. In the Netherlands, these persons are “REOB certified”, in Germany . In
each country, maintenance and location guideline may be present, there are described in local
standards such as:
Netherlands: REOB certified, NEN-2559 https://hetccv.nl/certificatie-inspectie/vakman/onderhoud-
blusmiddelen/
Belgium: NBN S -050 21
Germany: DIN 14406
Austria: önorm F-1053
UK: BS 5306-3:2009
All local standards are based on product standard EN-3 and give specific information on where to
place extinguishers or how often to maintain them.
For consumers in most European homes, owning a fire extinguishers is not obligatory. Keeping a fire
extinguisher nearby to extinguishing a small, starting fire could however save lives and prevent a lot
of damages. The Dutch fire fighters advise consumers to only fight fires that have the size of a
football. If the fire is bigger, evacuate everyone from the building and call the fire fighters.
Testing and filling instructions
These instructions cover the most basic guidelines to test and refill a Smartwares extinguisher. The
powder extinguisher BB series, foam extinguisher SB series and wet chemical extinguisher VB series
are stored pressure extinguishers. They consist of a cylinder containing the extinguishing agent
(powder, foam or a wet chemical solution) and are permanently pressurized.
Visual inspection
The purchasing date sticker that is included with the extinguisher allows you to mark the installation
date as a reminder. Starting from installation a visual inspection is necessary because the extinguisher
is no longer protected by the giftbox.
Every 3 months check if the safety pin is still in place and read the pressure gauge (manometer) on ,
the extinguisher. This is not applicable for CO2 extinguishers, they do not have a pressure gauge The .
pressure gauge needle must be in the green area. If a rubber hose is present, check the hose for
corrosion and other damages. The instructions on the extinguisher should be readable, the