Lutron FCJS-010 Bruksanvisning
                    Lutron
                    
                    Smart hjem
                    
                    FCJS-010
                
                                
                
                
                                
                Les nedenfor 📖 manual på norsk for Lutron FCJS-010 (8 sider) i kategorien Smart hjem. Denne guiden var nyttig for 31 personer og ble vurdert med 5.0 stjerner i gjennomsnitt av 16 brukere
                        Side 1/8
                    
                    
                    
Radio Powr Savr 
Occupancy  
Sensor
Pico  
Remote 
Control
PowPak  
Dimming 
Module
30 ft 
(9 m) max
40 ft (12 m)
30 ft (9 m)
PowPak  
Dimming Module
Install in center of room to  
maximize RF coverage.
  A
  Connect mains wiring (switched hot, neutral) to each fixture.
B
  Connect 0 –10 V- control (+ and – ) to each fixture.
1
+
–
NEU
HOT
Class 2
MAINS
Fixture Earth
Green/Yellow
To additional 0 –10 V- fixtures
Neutral
Switched Line/Hot
Violet
Pink*
+
–
WARNING! Shock Hazard. May result in serious injury or death. Turn off power at circuit 
breaker before installing the unit.
Sample  
ballast shown
  Start Here
Mount, Wire, and Install 0 –10 V- Devices 
and Lighting Fixtures
Consult third-party device installation guide
2
A
  PowPak Dimming Module with 0 –10 V- can be installed on a junction box or marshalling box using the conduit nut (provided) or with mounting 
screws (not provided). The device must NOT be mounted inside a fixture or other metallic enclosure – only on the exterior of a fixture. Please 
consult local and national electric codes for proper installation.
If installing unit inside a junction box, please see Application Note #423 (P/N 048423 at www.lutron.com).
B
  Once installed, energize the PowPak Dimming Module with 0 –10 V-.
C
  Use the Toggle button “ u”  to toggle between high-end and OFF to verify ballast wiring.
D
  Use the Raise “
▲
” and Lower “
Δ
” buttons to verify control wiring.
Install PowPak Dimming Module with 0 –10 V-
Suggested Installation Location: Center of room to ensure proper RF coverage of area.
Switched Line/Hot (Red)
–
Line/Hot 
(Black)
To Fixtures
0 –10  V- to Fixtures*
Neutral (White)
+
Neutral
Junction Box
1/2 in (21 mm) Knockout Opening
Conduit Nut
RMJS-8T-DV-B / URMJS-8T-DV-B
Switched Line/Hot (Red)
–
Line/Hot 
(Black)
To Fixtures
0 –10  V- 
to Fixtures *
Neutral (White)
+
Neutral
Junction Box
1/2 in (21 mm) Knockout Opening
Conduit Nut
RMJS-8TN-DV-B
Switched  Line / Hot  (Red)
–
Line / Hot  (Black)
To Emergency 
Fixtures
0 –10  V- to 
Emergency 
Fixtures*
Neutral (White)
+
Neutral
Junction Box
1/2 in (21 mm) 
Knockout Opening
Conduit Nut
Emergency  
Backup 
Generator
Automatic  
Transfer  
Switch
Regular  
Utility Power
Neutral 
120 / 277  V~  Normal Feed
Neutral 
120 / 277  V~  Emergency Feed
Note:  For periodic testing and maintanance of emergency systems, use the toggle button of 
the RMJS-8T-DV-B-EM to ensure proper operation. Make sure PowPak buttons remain 
accessible.
Note:  Momentary power outages can envoke emergency mode on the dimming module. See 
Troubleshooting section for details.
RMJS-8T-DV-B-EM
*  Use 18 AWG to 16 AWG (0.75mm
2
 to 1.5mm
2
) solid wire only
vive.lutron.com
X
Programming with a Vive Hub
3
 A
  Use an iOS® or Android®  
compatible device.
 C
  Open the app and follow 
the instructions.
     Note: For further information on set up, 
programming, and troubleshooting with a 
Vive system, please refer to the installation 
instructions included with the Vive hub or 
visit www.lutron.com/vive
     Note: For programming the PowPak 
Dimming Module without a Vive hub see 
reverse side.
X
Vive
 B
  Download the Lutron  
Vive app.
041588 
Rev. A
09/2020
PowPak | Installation
Dimming Module with 0 –10 V-
English
All Wireless  
Transmitters must  
be installed within 30 ft  
(9 m) of the PowPak Dimming  
Module with 0 –10 V-.
0 –10  V- Control: 10 V-  60 mA
UL 2043 Plenum Rated
UL 924 Listed (RMJS-8T-DV-B-EM) 
Compatible with ANSI E1.3 2001 (R2006), IEC 60929 Annex E
120 / 277  V~  50 / 60 Hz  8 A
RMJS-8T-DV-B
URMJS-8T-DV-B
RMJS-8TN-DV-B
Important Notes: Please read before installing.
For installation by a qualified electrician in accordance with all local and 
national electrical codes (including periodic testing and maintenance of 
emergency systems).
•  Note: Use copper conductors only.
•  Check to see that the device type and rating is suitable for the application.
•  DO NOT install if product has any visible damage.
•  If moisture or condensation is evident, allow the product to dry completely 
before installation.
•  Operate between 32 °F and 104 °F (0 °C and 40 °C) ambient.
•  0% to 90% humidity, non-condensing.
•  For indoor use only.
Note for Replacement:
RMxS and URMxS - the "S" model can replace the non-"S" model
041771 
Rev. A 
09/2020
Part of the Vive Family
120 / 277  V~  50 / 60 Hz  8 A
RMJS-8T-DV-B-EM
  IMPORTANT SAFEGUARDS
  When using electrical equipment, basic safety precautions should always be  
followed including the following:
  READ AND FOLLOW ALL SAFETY 
INSTRUCTIONS.
•  Do not use outdoors.
•  Do not mount near gas or electric heaters.
•   Equipment should be mounted in locations and at heights where it will not be 
subjected to tampering by unauthorized personnel.
•   The use of accessory equipment not recommended by the manufacturer may  
cause an unsafe condition.
•  Do not use this equipment for other than its intended use.
  SAVE THESE INSTRUCTIONS
Test
Link
Cal.
+
For each system, ensure that you have:
One PowPak Dimming Module At least one Wireless Transmitter At least one 0 –10 V- Fluorescent Ballast or LED Driver
Required Components
Radio Powr Savr Occupancy / Vacancy Sensor 
(10 maximum)
Radio Powr Savr Daylight Sensor
(1 maximum)
Pico Remote Control
(10 maximum)
60 mA maximum for the control lines. Switches up to 8 A total.  
May be pre-installed in light fixture.
Note: All drivers and ballasts used with Vive wireless controls must comply with the 
limits for a Class A device, pursuant to Part 15 of the FCC rules.
PowPak Dimming Module with 0 –10 V-  
(1 maximum)
Raise
Toggle
Lower
Load Status LED
Consult third-party 0 –10 V- fixtures installation guide for fixture-specific wiring.
For mounting and wiring best practices see Lutron Application Note #620 (P/N 048620).
+
Customer Assistance   www.lutron.com/support     
Wireless Controls: All lights
Default Functionality
Daylight Sensor
All lights dim in response to daylight.
On: 100% ; Favorite: 50%; Off: 0% 
Occupancy Sensors
Occupied: All lights100% ; Unoccupied: All lights off
Lutron Electronics Co., Inc. | 7200 Suter Road 
Coopersburg, PA 18036-1299, U.S.A.
* This wire may be gray on older products or in retrofit applications.
Produkspesifikasjoner
| Merke: | Lutron | 
| Kategori: | Smart hjem | 
| Modell: | FCJS-010 | 
| Bruksanvisning: | Ja | 
| Tilkoblingsteknologi: | Trådløs | 
| Antall per pakke: | 1 stykker | 
| AC-inngangsspenning: | 120 - 277 V | 
| Produktfarge: | Green, White | 
| Pakkedybde: | 32 mm | 
| Pakkehøyde: | 87 mm | 
| Pakkebredde: | 48 mm | 
| Arbeidsfrekvens: | 431 - 437 MHz | 
| Overføringsavstand: | 9 m | 
Trenger du hjelp?
Hvis du trenger hjelp med Lutron FCJS-010 still et spørsmål nedenfor, og andre brukere vil svare deg
Smart hjem Lutron Manualer
                        
                         26 Februar 2025
                        
                    
                                                            
                        
                         27 Desember 2024
                        
                    
                                                            Smart hjem Manualer
- Govee
- Ferguson
- Asus
- Vimar
- Homematic IP
- Burg-Wachter
- Somfy
- Honeywell
- Delta Dore
- Middle Atlantic
- Kogan
- TP Link
- Hager
- Philips
- Winland
Nyeste Smart hjem Manualer
                        
                         30 Mars 2025
                        
                    
                                                            
                        
                         30 Mars 2025
                        
                    
                                                            
                        
                         30 Mars 2025
                        
                    
                                                            
                        
                         28 Mars 2025
                        
                    
                                                            
                        
                         19 Mars 2025
                        
                    
                                                            
                        
                         18 Mars 2025
                        
                    
                                                            
                        
                         12 Mars 2025
                        
                    
                                                            
                        
                         10 Mars 2025
                        
                    
                                                            
                        
                         7 Mars 2025
                        
                    
                                                            
                        
                         26 Februar 2025