Tripp Lite SU6000XFMR2UTAA Bruksanvisning

Tripp Lite Ikke kategorisert SU6000XFMR2UTAA

Les nedenfor 📖 manual på norsk for Tripp Lite SU6000XFMR2UTAA (16 sider) i kategorien Ikke kategorisert. Denne guiden var nyttig for 6 personer og ble vurdert med 4.5 stjerner i gjennomsnitt av 2 brukere

Side 1/16
Owner’s Manual
SmartOnline
®
Series 6kVA
Isolation/Step-Down
Transformer Module
(Series Number: AGAC7579)
Not suitable for mobile applications.
PROTECT YOUR INVESTMENT!
You could also win an ISOBAR6ULTRA surge protector—a $100 value!
www.tripplite.com/warranty
1111 W. 35th Street, Chicago, IL 60609 USA • www.tripplite.com/support
Copyright © 2017 Tripp Lite. All rights reserved.
Important Safety Warnings 2
Mounting 2
Features 4
Service 5
Warranty and Product Registration 5
Español 6
Français 11
2
SAVE THESE INSTRUCTIONS.
This manual contains important instructions and warnings that should be followed during the installation and maintenance of
Tripp Lite SmartOnline transformer modules. Failure to heed these warnings may affect your warranty.
Transformer Location Warnings
Install your transformer module indoors, away from excess moisture or heat, direct sunlight, dust or conductive contaminants.
Install your transformer module in a structurally sound area. Your transformer is heavy; exercise care when moving or lifting the unit.
Only operate your transformer module at indoor temperatures between 32° F and 104° F (0° C and 40° C). For best results, maintain
indoor temperatures between 62° F and 84° F (17° C and 29° C).
For proper ventilation, leave adequate space around all sides of the transformer module.
Do not install the transformer module near magnetic storage media, as this may cause data corruption.
Equipment Connection Warnings
Installation should only be performed by qualified service personnel.
CAUTION: To reduce the risk of fire, connect only to a circuit provided with a 30A branch circuit overcurrent protection in accordance with
the National Electrical Code, ANSI/NFPA 70 and the Canadian Electrical Code, Part I, C22.1. Short circuit backup protection overcurrent
protection is provided by the building installation. Be sure to use the proper overcurrent protection for the installation in accordance with
the plug/equipment rating.
Be sure to provide a local disconnect device on any models that are permanently installed without a plug that is easily accessible.
Connect your transformer module's grounding terminal to a grounding electrode conductor.
Branch circuit protection must be provided by building installation per your National/Local Electrical Code. Only connect a circuit provided
with 30 amperes maximum over current protection.
Warning! Input voltage selector switch must be set to match the source voltage before applying power. The selector switch is
located behind the front bezel and is preset to 208V~.
Maintenance Warnings
Your transformer module does not require routine maintenance. Do not open it for routine maintenance. There are no user-serviceable
parts inside.
Medical Applications and Life Support Warning
Use of this equipment in life support applications where failure of this equipment can reasonably be expected to cause the failure of the
life support equipment or to significantly affect its safety or effectiveness is not recommended.
1
A
B
B
Important Safety Warnings
Mounting (Rack)
Mount your equipment in either a 4-post or 2-post rack or rack enclosure.The user must determine the fitness of hardware and procedures
before mounting. If hardware and procedures are not suitable for your application, contact the manufacturer of your rack or rack enclosure.
The procedures described in this manual are for common rack and rack enclosure types and may not be appropriate for all applications.
WARNING!
Transformer modules are extremely heavy! Use caution while lifting and mounting! User must properly stabilize
the module while lifting and mounting!
4-Post Mounting
1
Connect the two segments of each shelf
A
using the included attached screws and
wing nuts
B
. Leave the screws slightly loose so that the shelves can be adjusted in
the next step.
3
2
3
C
F
E
G
4
H
2
Adjust each shelf to fit your rack, then mount them in the lowest available space of
your rack with the screws, nuts and washers provided
C
. Note that the support ledges
should face inward. Tighten the wingnuts that connect the shelf segments
D
.
3
Attach mounting ears
E
to the front mounting holes of your equipment
F
using the
screws provided
G
. The ears should face forward.
4
Using an assistant, lift your equipment and slide it onto the mounting shelves. Attach
your equipment to the rack by passing the screws, nuts and washers (user-provided)
H
through its mounting ears and into the rack rails.
D
The transformer module can be mounted in an upright tower position when used with optional base stands, sold separately by Tripp Lite
(model: 2-9USTAND). When installing a transformer module, place it between the power module and the battery module.
WARNING!
Transformer modules are extremely heavy! Use caution while lifting and mounting! User must properly stabilize
the module while lifting and mounting!
Mounting (Tower)
Mounting (Rack)
2-Post (Telecom) Mounting
To mount your equipment in a 2-post rack, you must purchase a Tripp Lite 2-Post Rackmount Installation Kit (model: 2POSTRMKITWM, sold
separately). See the Installation Kit's owner's manual for complete mounting instructions.

Produkspesifikasjoner

Merke: Tripp Lite
Kategori: Ikke kategorisert
Modell: SU6000XFMR2UTAA
Vekt: 32658 g
Bredde: 431.8 mm
Dybde: 533.4 mm
Høyde: 76.2 mm
Bruksanvisning: Ja
Opprinnelsesland: Taiwan
Pakkevekt: 37194 g
Sertifisering: TAA Compliant
Utgangseffekt: 6000 W
Utgangsspenning (maks.): 240 V
AC-inngangsspenning: 208 V
AC-inngangsfrekvens: 60 Hz
UPS topologi: Standby (Offline)
Inngangsspenning (maks.): 240 V
Produktfarge: Sort
Pakkedybde: 685.8 mm
Pakkehøyde: 203.2 mm
Pakkebredde: 558.8 mm
Bærekraftsertifikater: RoHS
Formfaktor: Rackmontering/tårn
Inngangsfrekvens: 60 Hz
Kroppsmateriale: Stål
Relativ luftfuktighet under drift (H-H): 0 - 95
Rack-montering: Ja
Dekselfarge: Sort
Antall AC outlets: 240 AC-utganger
Masterkassens (ytterkassens) bruttovekt: 37470 g
Masterkassens (ytterkassens) lengde: 685.8 mm
Produkter per masterkasse (ytterkasse): 1 stykker
Masterkassens (ytterkassens) bredde: 558.8 mm
Masterkassens (ytterkassens) høyde: 223.5 mm
AC-utgangstyper: Terminal
Strømuttak: Terminal
Rack-montert sett: Ja
Output strømkapasitet (VA): 6 kVA
Inngangsspenning (min.): 208 V
Utgangsspenning (min.): 208 V
Belastningskapasitet: 6000 VA
Inngangsstrøm (maks): 30 A