Avtec AXWO Bruksanvisning

Les nedenfor 📖 manual på norsk for Avtec AXWO (5 sider) i kategorien Ikke kategorisert. Denne guiden var nyttig for 2 personer og ble vurdert med 4.5 stjerner i gjennomsnitt av 2 brukere

Side 1/5
OPERATOR MANUAL
IMPORTANT INFORMATION, KEEP FOR OPERATOR
888-994-7636, fax 888-864-7636
uniedbrands.net
PART NUMBER PP MNL2207, REV. A (08/23)
This manual provides information for:
VENTILATION SYSTEMS
THIS MANUAL MUST BE RETAINED FOR FUTURE REFERENCE. READ,
UNDERSTAND AND FOLLOW THE INSTRUCTIONS AND WARNINGS CONTAINED
IN THIS MANUAL.
FOR YOUR SAFETY Do not store or use gasoline or other ammable vapors
and liquids in the vicinity of this or any other appliance.
NOTIFY CARRIER OF DAMAGE AT ONCE It is the responsibility of the
consignee to inspect the container upon receipt of same and to determine
the possibility of any damage, including concealed damage. Avtec suggests
that if you are suspicious of damage to make a notation on the delivery
receipt. It will be the responsibility of the consignee to le a claim with the
carrier. We recommend that you do so at once.
Manufacture Service/Questions 888-994-7636.
RETAIN THIS MANUAL FOR FUTURE REFERENCE
NOTICE: Due to a continuous program of product improvement, Avtec reserves the
right to make changes in design and specications without prior notice.
NOTICE: Please read the entire manual carefully before installation. If certain
recommended procedures are not followed, warranty claims will be denied.
MODEL NUMBER _________________________
SERIAL NUMBER _________________________
INSTALLATION DATE ______________________
INSTALLATION INSTRUCTIONS
Avtec hoods are provided with adjustable hanging brackets designed to receive
1/2” threaded rod with a 1/2” nut and washer. Supporting rods must be
connected to all factory installed brackets. Recommended hanging height is 6’-
6” above nished oor for canopies. Low side wall ventilators should be installed
directly upon a Avtec base or on a re rated wall. If wall mounted, the bottom of
the vent should be 36” above nished oor.
ALL AVTEC VENTILATION SYSTEMS MUST BE INSTALLED IN ACCORDANCE
WITH NFPA-96, REMOVAL OF SMOKE AND GREASE-LADEN VAPORS FROM
COMMERCIAL COOKING EQUIPMENT.
BAFFLE FILTER (AF) SERIES
Model AF ventilators are listed by UL and are built in accordance of NFPA-96
for use with UL listed re extinguishing systems for duct hood protection. They
are available with or without an automatic re damper. They utilize UL classied
removable bafe lters to extract grease and provide a limited re barrier. The
canopy contains a hidden grease trough and removable cup. Surface, plenum
and duct collar re extinguishing systems may be factory supplied.
MODULAR GREASE EXTRACTORS (AX) SERIES
Model AX ventilators are listed by UL and are built in accordance of NFPA-96 for
use with UL listed re extinguishing systems for duct hood protection. They are
available with or without an automatic re damper. These models utilize high
velocity removable grease extractors. The canopy contains a hidden grease
trough and removable cup. Surface, plenum and duct collar re extinguishing
systems may be factory supplied.
FIGURE 1
FIGURE 3 FIGURE 4
HOOD FACE
T-MOLDING
C-CHANNEL
FIGURE 2
INSULATED
SUPPLY DUCT
FIRE DAMPER &
VOLUME CONTROL
DAMPER
FLUID WEL
D
EXHAUST DUCT
ACCESS
PANEL
FRONT OR BACK
NOTE: HOLES DRILLED THROUGH HOOD ANGLE BY
INSTALLER AFTER BRACKET ATTACHMENT
POINTS HAVE BEEN DETERMINED.
HOOD
ANGLE
OF HOOD
HANGER BRACKET DETAIL
HANGER ROD
PRE-DRILLED
HOLE, ACCEPTS
UP TO 1/2"ÿ ROD
5/16" BOLT
HOLE, ACCEPTS
PRE-DRILLED
NUT
HANGER ROD
S.S. NUT & BOLT
BY OTHERS
Information contained in this document is known to be current and accurate at the time of printing/creation. Reference our product line website for the most updated
product information and specications. © 2023 Electrolux Professional, Inc. All Rights Reserved.
2 OM-VENTILATION SYSTEMS
EXHAUST
DUCT IS
FLUID
WELDED
TO
COLLAR
GREASE
TERMINATOR
OR
GREASE TROUGH
CEILING
EXHAUST DUCTALL WELD
CONSTRUCTION
HING
40" MINIMUM
10' - 0" MINIMUM
IMPORTANT - READ FIRST - IMPORTANT
CAUTION: DO NOT ATTEMPT TO SERVICE THIS UNIT YOURSELF AS REMOVING COVERS
MAY CAUSE UNNECESSARY EXPOSURE TO DANGEROUS VOLTAGE.
CAUTION: NEVER CONNECT THE UNIT TO A POWER SOURCE WHILE STANDING IN
WATER. WET HANDS AND WET FLOORS SHOULD BE AVOIDED WHEN
CONNECTING ANY ELECTRICAL APPLIANCE TO A POWER OUTLET.
CAUTION: FANS MAY HAVE MULTIPLE POWER CONNECTIONS. MAKE SURE ALL FANS
ARE ISOLATED FROM POWER PRIOR TO PERFORMING MAINTENANCE.
AUTO WASH DOWN (AW) SERIES
Model AW ventilators are listed by UL and are built in accordance of NFPA-96 for use
with UL listed re extinguishing systems for duct hood protection. They are available
with or without an automatic re damper. These systems utilize a high velocity grease
extractor and an integral water wash system cleans the inside of the grease
extraction chamber either by manual activation of the Wash Start button or by a
programmable timer. The duration of the wash is electronically controlled. The
wash system is also activated by an electrical thermostat or a manual switch in
the event of a re condition. A surface re extinguishing system is required and
may be factory supplied.
CANOPIES
1. Check all local codes prior to installation. Special requirements may be
necessary depending upon building material construction.
2. Move crated hood to location of installation and very carefully uncrate hood.
3. Raise hood to proper hanging height.
4. Suspend hood from adequate roof supports using 1/2” threaded rods with
nuts and washers (See Fig. 1).
5. Level hood left to right and front to back.
6. Brackets are provided for hoods which are to be installed end to end or back
to back. Bolt brackets together using 3/8” bolt through holes provided (See
Fig. 2).
7. Install C channel where the ends of the hood meet and install T moldings on
front face of hoods where they join. High temperature silicone can be used
to install channel and T moldings (See Fig. 3).
8. For make-up air hoods, the supply collar with built-in UL listed re damper
and air volume damper must be installed per instructions on collar.
9. Provide a removable service door in supply duct near re damper (See Fig.
4).
EXHAUST FAN & DUCT
1. Check all local codes prior to installation.
2. All exhaust fans are supplied with a hinge kit and grease box.
3. The exhaust fan curb should be installed directly above the hood if possible.
Always maintain the shortest duct run possible.
4. Cut hole and seal exhaust fan curb to roof.
5. Duct shall be sized to provide air velocities not exceeding 1200 FPM.
6. Install hinges and airline cable on exhaust fan cap and metal curb.
Remember to leave ample room for fan to tilt back. Fan will remain in tilted
back position.
7. Install grease collection box on side of fan that has grease tube discharge.
8. The exhaust duct must be constructed of 16 gauge carbon steel or 18 gauge
stainless steel. All seems must be uid welded.
9. A duct transition should be provided below exhaust fan inlet.
10. The exhaust duct must be uid welded to hood collar.
11. Make all necessary electrical connections and check fan for proper rotation.
NOTE: Fan will exhaust air running in wrong direction.
WALL ATTACHMENT
Control panels are provided with all auto wash type ventilators (Model AW) and
are optional with all bafe lter type (AF) and modular grease extractor type (AX).
Control panels with models (AF) and (AX) do not have the auto wash plumbing
assembly compartments.
Control panel dimensions and connection detail are shown on the enclosed shop
drawing. Panels may be surfaced mounted, partially recessed or fully recessed.
FIGURE 5
FIGURE 6 FIGURE 7
A
A
B
B
FIGURE 8 FIGURE 9
ENCLOSURE TOP
ENCLOSURE
SIDE
FIGURE 10 FIGURE 11
78" A.F.F.
END SEAM CAP
CENTER SEAM CAP
END SEAM CAP
SUPPLIED STAINLESS BOLTS
AND ACORN NUTS
3 OM-VENTILATION SYSTEMS
SURFACE MOUNTED
Drill four holes in ventilator plumbing compartment as required. Be careful not
to damage any components. Avoid drilling into electrical compartments. Bolt to
wall with anchor bolts or other acceptable means. Weight of control panel varies
from 90 to 200 lbs.
RECESSED MOUNTED
Cut hole in wall 1/2” greater than overall dimensions of the control box (sho wn on shop
drawing). Spacers or support angles may be necessary to provide proper support. It
is recommended that the panel be bolted to wall similar to method used for
surface mounted above.
PAWS CONTROL PANEL
The Programmable Automatic Wash Sequence (PAWS) panel is designed to
control the operation of the ventilator exhaust and make-up air fans and wash the
grease extraction plenum with hot water/detergent solution. The fan operation
and wash sequence can be started and stopped manually or programmed for
automatic operation.
FRESH AIR SUPPLY FAN (See Fig. 5)
Pieces provided. One or two optional side skirts may be provided.
1. Check all local codes prior to installation.
2. Supply fan inlet must be located to minimum 10’-0” from the exhaust fan. If
10’ is not possible a 3’ vertical separation may* be acceptable.
3. Cut and seal supply fan curb to roof.
4. Duct shall be constructed of 22 or 24 gauge steel. Insulated duct material
should be used to eliminate frost and/or condensation.
5. Duct shall be sized to provide air velocities not exceeding 1200 FPM.
6. A volume control damper, provided in the duct just above the supply collar that
contains the UL listed re damper, should be properly set to supply CFM
required.
7. If the hood is provided without the supply collar installed, it must be installed
per the instructions provided on the collar.
8. Carefully place the supply fan on roof curb. Face supply fan inlet away from
prevailing winter wind. Electrical back draft damper is recommended in cold
climates.
9. Bolt or screw fan to fan curb.
10. Make all necessary electrical connections and check fan for proper rotation.
NOTE: Fan will supply air running in wrong direction. *Dependent on local code
requirements.
SIDE SKIRTS (See Fig. 6)
1. Side skirts are offset at the top and have a 90° bend inward at the rear.
2. Skirts are to overlap the outside of the hood. Bolts and acorn nuts should be
attached per the drawing (stainless bolts and acorn nuts supplied).
3. Skirt ange should be screwed to the wall (screws not provided).
TOP ENCLOSURE PANELS (See Fig. 7-9)
Pieces provided. Enclosure panels are provided for exposed side(s) of hood.
1. Hoods ordered with enclosure panels will be shipped with Z-clips welded
to the top perimeter of hood top where panels are to be installed. Nuts and
washers to connect front to sides are taped to the inside of one of the panels.
2. With a rubber mallet, tap 1” return ange into the Z-clip on all sides.
3. Attach sides to ends with provided panhead screws and nuts.
INSULATED WALL PANEL (See Fig. 12)
Pieces provided. Top panel will have a 1” ange full length top and bottom, and
interlocking slots located on the bottom. Bottom panel will have interlocking tabs
on top and full length 1” ange on bottom.
1. Install wall panels prior to hanging hood(s).
2. Install top panel rst at 6’-6” A.F.F. and level. Screw panel to wall making
sure slotted holes are facing oor.
3. Install lower panel by sliding tabs into slotted holes in upper panel, screw
bottom ange to wall.
4. Caulk horizontal seam with NSF approved silicone sealant.
5. When hood is hung it will rest on top panel.
NOTE: Be careful not to damage wall panel face when installing hood.
SINGLE THICKNESS WALL PANEL (See Fig. 13)
1. Install wall panels prior to hanging hood(s).
2. Install seam strips at proper locations and screw to wall.
3. Apply glue to wall between seam strips.
4. Slip one end of wall panel into seam strip, pull out middle of panel and slip other
end of panel into other seam strip. Gently apply pressure over entire wall panel to
secure to wall. Wall bands for side walls are provide with 1” return bend, which is
to be located behind rear wall panels.
START/CHECK/BALANCE
DIRECT DRAW HOODS
1. Close all doors and windows.
2. Operate all exhaust fans, even fans serving other hoods, make-up air units and
building HVAC.
3. Turn on all cooking equipment under the hood to preheat to operating
temperature.
4. Produce large quantities of smoke.
5. Observe capture of vapors.
6. If all vapors are not captured, increase exhaust fan RPM.
7. Check air pressure in kitchen. Pressure must be negative relative to dining
room pressure.
8. Air velocities entering the kitchen from the dining room should not exceed
100 FPM. No air should be moving toward the dining area.
9. Repeat steps 6 and 7 until all vapors are captured.
NOTE: The exhaust and supply (if any) air ow rates were established under
controlled laboratory conditions, and greater exhaust and/or lesser supply air
may be required for complete vapor and smoke removal in specic installations.
MAKE-UP AIR HOODS EXHAUST FAN(S)
1. Open all doors and/or windows leading to outside.
2. Start the exhaust fan only. Do not run the supply fan or make-up unit.
3. Refer to drawings and/or UL information label on hood for proper CFM
requirements.
4. Adjust speed of exhaust fan to obtain proper air velocities and CFM through
grease lters.
SUPPLY FAN OR MAKE-UP AIR UNIT
1. Start the supply fan and/or make-up unit only. Do not run the exhaust fan.
2. Refer to drawings or UL information label on hood for proper CFM
requirements.

Produkspesifikasjoner

Merke: Avtec
Kategori: Ikke kategorisert
Modell: AXWO

Trenger du hjelp?

Hvis du trenger hjelp med Avtec AXWO still et spørsmål nedenfor, og andre brukere vil svare deg




Ikke kategorisert Avtec Manualer

Avtec

Avtec AXWO Bruksanvisning

20 September 2025
Avtec

Avtec SSA-ISLE Bruksanvisning

11 September 2025
Avtec

Avtec SSA-PIZZA Bruksanvisning

11 September 2025

Ikke kategorisert Manualer

Nyeste Ikke kategorisert Manualer