Klein Tools CL445 Bruksanvisning

Les nedenfor 📖 manual på norsk for Klein Tools CL445 (56 sider) i kategorien måleinstrument. Denne guiden var nyttig for 2 personer og ble vurdert med 4.5 stjerner i gjennomsnitt av 2 brukere

Side 1/56
INSTRUCTION MANUAL
ENGLISH
FRANÇAIS pg. 37
ESPAÑOL pg. 19
HVAC Clamp Meter
True RMS
Measurement
Technology
DC MICROAMPS
INRUSH CURRENT
NON-CONTACT
VOLTAGE TESTING
AUTO-RANGING
TEMPERATURE
AUDIBLE CONTINUITY
5001748
750V
600V
600A
60M
Ω
2m
-148° –
1832°F
-100° –
1000°C
CL445
CAT IV
600V
HVAC Clamp Meter
True RMS
Measurement
INRUSH CURRENT
VOLTAGE TESTING
AUDIBLE CONTINUITY
HVAC Clamp Meter
AUDIBLE CONTINUITY
2
GENERAL SPECIFICATIONS
Klein Tools CL445 is an automatically ranging true root mean
square (TRMS) digital clamp meter that measures AC current and
inrush via the clamp, AC/DC voltage, DC microamps, resistance,
continuity, frequency, capacitance, and tests diodes via test leads, and
temperature via a thermocouple probe.
Environment: Indoor. DO NOT expose to moisture, rain, or snow.
Operating Altitude: 6562 ft. (2000m)
Relative Humidity: <95% non-condensing
Operating Temp: 32° to 122°F (0° to 50°C)
Storage Temp: 14° to 122°F (-10° to 50°C)
Accuracy: Values stated at 65° to 83°F (18° to 28°C)
Temp Coef cient: 0.1 × (Quoted Accuracy) per °C above 28°C
or below 18°C, corrections are required when ambient working
temp is outside of Accuracy Temp range
Dimensions: 9.24" × 3.77" × 1.59" (235 × 96 × 40 mm)
Weight: 12.58 oz (356.5 g) including batteries
Calibration: Accurate for one year
Auto Power-Off (APO): After approx. 10 minutes of inactivity
Standards: IEC/BS/EN 61010-1, 61010-2-032,
IEC/BS/EN 61326-1, 61326-2-2.
Conforms to UL STD.61010-1, 61010-2-032;
Certified to CSA STD.C22.2 NO. 61010-1,
61010-2-032.
Pollution degree: 2
Accuracy: ± (% of reading + # of least significant digits)
Safety Rating: CAT IV 600V
Class 2, Double insulation
Drop Protection: 6.6 ft. (2 m)
CAT III: Measurement category III is applicable to test and
measuring circuits connected to the distribution part of the
building’s low-voltage MAINS installation.
CAT IV: Measurement category IV is applicable to test and
measuring circuits connected at the source of the building’s low-
voltage MAINS installation.
Electromagnetic Environment: IEC EN 61326-1. This
equipment meets requirements for use in basic and controlled
electromagnetic environments like residential properties,
business premises, and light-industrial locations.
Specifications subject to change.
ENGLISH
5001748
3
ELECTRICAL SPECIFICATIONS
Function Range Resolution Accuracy
AC Voltage
(V AC)
600.0mV 0.1mV
±(1.8% + 5 digits)
6.000V 1mV
±(1.5% + 5 digits)
60.00V 10mV
±(1.2% + 5 digits)
600.0V 100mV
750V 1V ±(1.5% + 5 digits)
DC Voltage
(V DC)
600.0mV 0.1mV ±(1.0% + 8 digits)
6.000V 1mV
±(0.8% + 3 digits)
60.00V 10mV
600.0V 100mV ±(1.0% + 3 digits)
Input Impedance: 10MΩ
Frequency Range: 45 to 400Hz
Maximum Input: 750V AC RMS or 600V DC
AC Current
(A AC)
60.00A 10mA ±(2.5% + 10 digits)
600.0A 100mA ±(2.0% + 10 digits)
Frequency Range: 50 to 60Hz
DC Microamps
(µA DC)
600.0μA 0.1μA ±(1.2% + 5 digits)
Maximum Input: 750V AC RMS or 600V DC
Resistance
600.0Ω 0.1Ω ±(1.2% + 5 digits)
6.000kΩ
±(1.2% + 3 digits)
60.00kΩ 10Ω
600.0kΩ 100Ω
6.000MΩ 1kΩ
60.00MΩ 10kΩ ±(2.0% + 5 digits)
Maximum Input: 750V AC RMS or 600V DC

Produkspesifikasjoner

Merke: Klein Tools
Kategori: måleinstrument
Modell: CL445

Trenger du hjelp?

Hvis du trenger hjelp med Klein Tools CL445 still et spørsmål nedenfor, og andre brukere vil svare deg